# #laguna — 2026-02-04 **08:05 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770221144870769):** do you know which RW tank? where am i looking on scada? **08:05 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770221148030869):** (for the faltline) **08:18 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770221886150879):** ive confirmed that the jail RW water is updating.. i just watched its value changing **08:18 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770221888854009):** i'll keep looking **08:20 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1770222011130769):** The tanks at the plant **08:20 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770222021408669):** effluent / RW tanks? **08:20 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1770222029136479):** Yes **08:20 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770222032460019):** ok. **08:20 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770222035038409):** the value isnt updating? **08:20 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770222038205749):** or the trend isnt working? **08:20 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770222050158379):** i cant run trends remotely so its difficult to check **08:21 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1770222087875339):** Value isn't updating. It updates on old scada **08:21 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770222098895699):** ok, cool. i think i can work with that. **08:21 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770222101183739):** thank you **09:52 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770227555625169):** ![[F0ACJSFS563_image.png]] ![[F0ACY8R8YP8_image.png]] **09:52 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770227567095779):** @Kevin im trying to identify this PLC **09:52 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770227574432269):** DHP_ABPLC **09:53 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770227583866489):** do you know what the code folder may be called? **09:53 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1770227605882829):** the plc is the clearwell **09:53 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1770227613986289):** oh, wait **09:53 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770227615117949):** so. **09:53 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770227616942389):** yea. **09:53 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770227618258909):** no. **09:53 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770227631211489):** i found tags pointing to the clearewell PLC in old SCADA for level **09:54 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770227649003479):** but there are a dozen or so related tags for alarms and alarm setpoints for RW tank levels **09:54 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770227652263679):** that point to this PLC **09:54 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770227663780069):** the tags do not exist in the clearwell PLC **09:54 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770227690418919):** also curious why the level tags were set up pointing to this ABPLC instead of clearwell **09:54 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770227699764039):** ive fixed that.. and level is working **09:55 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770227712799749):** but they do not have setpoint control or alarm bits **09:58 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770227895751579):** ![[F0ACJTVQHGX_image.png]] **09:58 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770227904315819):** the alarm and setpoint tags resolve to values in whatever PLC that is. **09:58 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770227912903999):** but if level no longer lives there im afraid the alarms will not work **09:58 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770227919845459):** i need to sort out what happened **09:59 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1770227977242509):** if it helps, the analog input from the tank level transmitters goes into the clearwell plc **09:59 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770227993000279):** ive updated the level values to use the clearwell PLC. and thats working **10:00 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770228009083319):** they were set up to read a different F8 address from this ABPLC previously **10:00 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770228022167739):** but scada will be incomplete if i dont link up the rest of the tags **10:00 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1770228045443439):** copy! **10:01 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770228086355729):** alarms will not work and they will not have control over alarm setpoints **10:01 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770228103897179):** but level is now updating! so we are making progress **10:02 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770228133614259):** there are no alarm bits/setpoint tags in the clearwell PLC.. and no alarm logic either. **10:10 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1770228622295309):** are they in the chem_rm plc? **10:10 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770228630561759):** yep i literally just confirmed that **10:10 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770228651804509):** but the level is no longer being messaged to that PLC.. im assuming thats why it stopped updating on scada **10:10 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1770228659567839):** ah! **10:11 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1770228664023259):** why **10:11 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770228670155739):** carrolo **10:11 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770228681554919):** last update was from them i think **10:11 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1770228704684629):** I don't think they've updated the chem_rm plc **10:11 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770228710205509):** the clearwell PLC **10:12 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1770228728461159):** yes, right. but I think that was a year or more agao **10:12 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770228733862869):** ![[F0ACYDP2P6J_image.png]] **10:12 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770228744003039):** indeed. im not sure. **10:12 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1770228758393159):** this happened when I pulled the UF off the DH+ network **10:12 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770228758466869):** i cant confirm without being able to go online **10:12 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770228763115909):** ah **10:12 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770228765939669):** hm **10:12 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1770228771488929):** you can go online using the old scada pc **10:13 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770228787224009):** oh. we have RUT on there? **10:13 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1770228791539279):** yes **10:13 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770228794876209):** fantastic. **10:14 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1770228845843519):** I'm sure you remember, but I'll give you the warning anyway. If you go online with those, and then offline, and it asks you to save, ALWAYS save. **10:14 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770228858314209):** ![[F0ACU4212V9_image.png]] **10:14 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770228860582189):** this is the MSG i need to confirm **10:14 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770228871437179):** thanks for the reminder **10:14 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1770228890541299):** ok! **10:25 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770229505091049):** when you have a second can you try to connect to the laguna machine? and let me know the RUT#? im struggling to find the right machine **10:29 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770229784099629):** i found it **11:23 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770233022039899):** oops **11:24 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770233040050419):** that second message must have been added at some point.. on the branched rung **11:24 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770233047836339):** they are both executing at the same time **11:24 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770233060221289):** eventually this causes one of them to fail. and stay failed **11:24 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770233074136329):** i disabled the branched message and the first one started working again **11:24 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770233093626099):** i need to have the second one only trigger after the first one fails or succeeds **11:25 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770233111696329):** breaking apart the control word now to find the appropriate bits **11:26 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1770233164257259):** Ok **11:26 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1770233209242349):** I wonder why taking the UF off the network caused this **11:27 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770233225073569):** when re-enabling the second message it is working again. **11:27 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770233228527329):** i just dont know for how long **11:27 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770233235010899):** or what cauased them to collide **11:27 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1770233258547679):** Oh, so when I disconnected the cable it went into fail **11:27 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770233265316039):** MSG1 was locked out.. error message said disabled until link responds or something like that **11:27 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1770233270141589):** Then didn't recover **11:27 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770233272869369):** yeah **11:28 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1770233287313229):** Interesting **11:28 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1770233320942499):** Are alarms good now then? **11:28 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770233328783609):** im not done yet **11:28 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770233336582099):** but it should be back to normal **11:29 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770233345225659):** i'll have to put the tags back to this PLC instead of the clearwell PLC **11:29 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1770233351169119):** Copy **11:29 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1770233357444009):** Thanks! **12:18 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1770236332825439):** ok! i feel like thats all sorted out **12:51 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1770238302907919):** Ah good!

Extracted Entities

TypeKeyValueConfidenceEvidence
contact Person Mason Radke 100% 08:05 [Mason Radke]
contact Person Kevin 100% 08:20 [Kevin]
server Router RUT 80% when you have a second can you try to connect to the laguna machine? and let me know the RUT#?
site Client Plant Laguna 100% Client: Laguna
system PLC clearwell PLC 100% the analog input from the tank level transmitters goes into the clearwell plc
system PLC chem_rm plc 90% are they in the chem_rm plc?
system PLC DHP_ABPLC 90% DHP_ABPLC
system SCADA System old scada 90% Value isn't updating. It updates on old scada
system Network Device UF 80% this happened when I pulled the UF off the DH+ network
File: Clients/Laguna/Plant/slack/2026/02/2026-02-04_laguna.md