**11:56 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751482570249079):** @Mason Radke got a min?
**11:59 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751482762178549):** yes
**12:07 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751483227226889):** Do you have the code with you for the Laguna Jail Lift Station?
**12:07 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751483243489899):** yes
**12:07 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751483255925429):** We have gotten a few analog input 1 and analog input 2 fault alarms.
**12:07 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751483264019419):** Shown on the hmi
**12:07 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751483272404879):** Not sure what drives those
**12:07 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751483277173189):** ok.. let me take a look'
**12:08 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751483296900679):** Im onsite and getting connected
**12:08 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751483310179099):** There was no bump in the trend
**12:13 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751483588386649):** logix crashes every time i try to open the file
**12:13 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751483590801809):** im rebooting
**12:13 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751483599882029):** its in dropbox.. are you able to get online?
**12:14 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751483665882799):** Standby
**12:17 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751483855199699):** A Rockwell product that crashes? Huh.
**12:17 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751483861101229):** haha
**12:18 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751483885472169):** Mine just takes 10 min to come up
**12:20 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751484041164319):** Online. Uploading a fresh copy to Dropbox
**12:23 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751484182543859):** Its from the channel status bit
**12:23 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751484204417749):** hm
**12:23 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751484220619479):** Expansion IO
**12:23 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751484230101449):** what is the status?
**12:23 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751484234035929):** whats the bit represent
**12:24 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751484262720879):** Status now is running.
**12:25 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751484349300609):** im not sure what to do next.
**12:26 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751484374784439):** maybe put a longer delay on that alarm? maybe there are power issues? does it happen on power cycle?
**12:29 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751484588650229):** Power cycle. Good thought
**12:38 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751485137846819):** Power cycle does not do it
**12:39 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751485160049009):** im not sure on this one. its a staus bit on the IO channel?
**12:39 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751485166955569):** is it a boolean?
**12:39 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751485175073949):** Yes and yes
**12:41 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751485295575149):** and the description for that bit says that it represents running?
**12:41 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751485308346259):** No. There's no description
**12:42 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751485343316069):** you said earlier that the status is now "running"
**12:42 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751485350330239):** what does that mean
**12:42 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751485371400659):** That was on the Analog card configuration page
**12:43 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751485388520989):** there is a bit for each channel? or is it the card bit that triggers the alarm
**12:43 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751485414570429):** There is a status bit for each channel.
**12:43 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751485425550779):** ok, lets find out what that status bit represents.
**12:43 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751485433061159):** can you give me a screenshot and i'll do a little research
**12:45 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751485510103259):** Its the Local:2:I.Ch0Status
**12:45 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751485518889419):** Having trouble sending pics
**12:45 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751485550633309):** what is the IO card model?
**12:46 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751485615280379):** IF4
**12:47 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751485620405419):** 1769
**12:47 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751485670344819):** ok i think that is actually an int representing a status word
**12:47 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751485674893769):** anyway you can confirm?
**12:48 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751485704868939):** Local:2:I.Ch0Status.0 should go high when there is over or under-range
**12:48 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751485710239459):** .1 should go high on open circuit
**12:48 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751485718520129):** and .3 just indicates fault
**12:48 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751485726850239):** Style = decimal, Data Type = bool
**12:49 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751485760848829):** can i RUT to your machine?
**12:49 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751485778296659):** Standby
**12:50 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751485803222989):** Do you have the address?
**12:50 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751485825130779):** no. i do not
**12:52 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751485962024049):** 471-552-582-800
**12:52 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751485974182859):** I forgot the pw
**12:53 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751485980861709):** easy to reset
**12:53 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751486013211789):** autosys
**12:53 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751486032748989):** ok.. lets have a looksie
**12:54 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751486055835509):** so its an integer
**12:54 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751486058885359):** Its the one further down
**12:54 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751486067817889):** the first bit of the int?
**12:54 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751486075863949):** ooooh i see
**12:54 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751486081297319):** let me look into that one
**13:00 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751486410755249):** i think that goes high on any fault.. under range/ over range or any other data fault.
**13:00 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751486416000289):** looking for comfirmation
**13:00 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751486421413069):** how ofiten is it happening
**13:00 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751486442950969):** Sounds right
**13:01 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751486476790089):** It happened a few times yesterday, and once or twice on Saturday
**13:01 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751486488178579):** And it's both channels
**13:01 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751486505417319):** but the trend doesnt log any weird values?
**13:01 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751486515792269):** No.
**13:02 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751486524530589):** Could be faster than the trend
**13:02 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751486551974069):** what about putting a delay on the alarm.. its not affecting anything if we lose signal for 100ms right?
**13:02 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751486577747429):** if it gets worse we will start to get alarms or notice it in the trend
**13:03 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751486589317279):** if its just how its going to be then we can ignore it with the delay
**13:04 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751486670971569):** We could, not sure I like the idea though
**13:05 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751486725608469):** the alarm is logged on the HMI? its timestamped?
**13:05 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751486735235959):** does it say when it went active and when it cleared?
**13:05 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751486744097729):** wondering how long the bit is high for
**13:06 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751486804311839):** A fee seconds, except for the last time it tripped, it was out for 30 min
**13:06 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751486818206129):** But no weird trend
**13:07 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751486823128249):** yeah thats weird.
**13:07 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751486829157439):** so its not under range or overrange
**13:07 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751486842869389):** or open loop
**13:07 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751486871343209):** Right
**13:08 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751486910810659):** Card fault?
**13:09 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751486989464389):** Can we make it log the individual faults?
**13:13 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751487187073899):** is it easier if we this work through autosys or nviro? or does it matter?
**13:13 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751487202082239):** need to switch over my time tracker thing since its gonna takea. bit
**13:13 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751487207226589):** Your pick
**13:13 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751487216634309):** ok standby.
**13:16 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751487395631209):** Think I found it
**13:16 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751487404560609):** yeah they're both high right now
**13:17 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751487421668249):** I was jiggling wires
**13:17 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751487431610139):** Let me check further
**13:17 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751487434955799):** copy
**13:29 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751488166799369):** Loose connection on a jumper. But now pumps won't start. Still looking
**13:29 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751488181425239):** nice!
**13:29 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751488187727529):** this was a weird one, it had to be something like that
**13:30 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751488254851309):** i see the outputs lit up for the pump starts
**13:34 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751488489406749):** Level is reading when I have the fuse open
**13:35 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751488503757839):** how could that be
**13:35 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751488530293599):** AI card?
**13:35 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751488553615009):** why cant we send images here on slack anymore?
**13:36 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751488567657279):** i see 3.2ma and a scaled -1.7325 value
**13:36 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751488570960749):** unchanging
**13:36 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751488611572709):** Why are there two scalings?
**13:37 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751488630029989):** Oh
**13:37 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751488657711779):** Put fuses back
**13:38 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751488693694719):** i dont remember this one very well.. i feel like the code was already started? this doesnt look like mine
**13:38 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751488711945829):** We converted it from a ML1400
**13:39 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751488768100429):** i should have rewritten and converted at the same time like ive been doing for AMWC
**13:39 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751488776837049):** it i making sense to you?
**13:39 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751488779600039):** is it
**13:39 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751488785811509):** how are we looking
**13:40 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751488806591669):** Im going to pull the transmitter. We have a low level but says we are at 12 ft
**13:40 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751488831212759):** copy
**13:47 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751489239661839):** Not a xmtr issue. Something with low level switch.
**13:47 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751489256243749):** low level switch making the transmitter read 9ma?
**13:47 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751489265171059):** No. Level is correct
**13:47 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751489269256869):** ah
**13:47 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751489270508609):** i see
**14:06 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751490386015459):** i was able to stay busy enough on other things and i havent done anything to help.. im not billing any time to this
**14:09 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751490550130639):** Alright thanks. It does appear that there is a level transmitter issue as well.
**14:09 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751490558549829):** oh interesting
**14:09 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751490587171649):** Thanks for your help.
**14:10 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751490602106499):** tried to help!
**14:10 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751490617949999):** glad you found some things instead of chasing ghosts
**14:10 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751490640650659):** Me too
**14:16 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751491001917529):** The ML1400 we translated this from was my code.
**14:17 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751491028110499):** ah. I did the conversion in a weird way.
**14:17 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751491036400369):** maybe i used a conversion tool to get it started
**14:17 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751491041861259):** Likely
**14:17 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751491049997819):** i dont like tools.
**14:17 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751491055603499):** i like my own code
**14:18 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751491088535099):** I think Reno may have done the conversion. But you did the startup
**14:18 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751491102570289):** ah
**14:18 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751491111711029):** that might sound right
**17:54 [Kevin](https://slack.com/archives/C08JS6KDLBD/p1751504068218689):** Got things all fixed up. It was the loose wire, then I found the level transmitter was off by like 4 feet. Pulled it up and it was loaded with sludge and grease. Got that fixed, then pump 1 wouldn't start from the PLC. Found a blown fuse on the DO. Lots of fun stuff!
**17:54 [Mason Radke](https://slack.com/archives/C08JS6KDLBD/p1751504091165009):** earning that paycheck today