| contact |
Technician |
Kevin |
90% |
09:52 [Kevin]: Yeah. I'll go by and take a look |
| contact |
Technician |
Mason Radke |
90% |
09:53 [Mason Radke]: copy.. im available to log in.. let me know what you find |
| site |
Plant or Location |
south-county |
90% |
#south-county — 2026-01-30 |
| system |
SCADA System |
Win911 |
90% |
Should be counting... 60 second callout delay from win911 |
| system |
PLC System |
CTRL-RM PLC |
90% |
The cntrl-rm PLC has outputs that trigger lights on the old alarm board |
| system |
PLC System |
CCT PLC |
80% |
I'm going to cause a comm fail for CCT and we can see what happens. |
| task |
Adjust alarm severity |
Changed MCC, INF, and CCT comm fail severity to 900 |
90% |
i changed them all to severity 900 |
| task |
Reset alarm board |
Hit reset on alarm board to clear comm alarm light |
90% |
Oh ..I needed to hit the reset on the board |
| task |
Test alarm callout |
Test comm fail alarm callout after severity change |
80% |
do you want to test again? |
| task |
Power cycle CCT PLC |
Consider power cycling CCT PLC to resolve low memory issues |
80% |
Do I need to power cycle CCT? might help temporarily |