← Tough

Clients/Tough/SMR/slack/2025/09/2025-09-09_tough-smr.md

slack
Source
1
Chunks
8
Entities
Doc
Type

Content

# #tough-smr — 2025-09-09 **11:02 [Mason Radke](https://slack.com/archives/C08NFJSU753/p1757440959208739):** @Kevin are you onsite now? **11:03 [Kevin](https://slack.com/archives/C08NFJSU753/p1757441038177339):** No **11:04 [Mason Radke](https://slack.com/archives/C08NFJSU753/p1757441090227539):** ok, are you planning on being there today? i should be able to make some time to work on well 6 **11:05 [Kevin](https://slack.com/archives/C08NFJSU753/p1757441146316449):** Yes I will be there **11:06 [Kevin](https://slack.com/archives/C08NFJSU753/p1757441180014019):** I don't know what the problem could be if both vfds are programmed the same **11:09 [andy](https://slack.com/archives/C08NFJSU753/p1757441342747159):** I finished my cambria thing right now I’m gonna pack and head down and grab lunch and I’m gonna try to reset the VFD and redownload the program, that has caused issues before. I have been also told that if the inputs are high when the program goes in that the high state becomes normal and it causes problems. So I have to take down the control voltage on the VFD when I push the program. **11:10 [Mason Radke](https://slack.com/archives/C08NFJSU753/p1757441420435479):** there are status parameters that will help us identify speed reference source. **11:10 [Mason Radke](https://slack.com/archives/C08NFJSU753/p1757441433398369):** and other things.. let me know if you guys want me to hop on when you're there and look around **11:34 [andy](https://slack.com/archives/C08NFJSU753/p1757442875603069):** I have one stop to make. I’ll probably be there around 1:30. I don’t know Kevin when you were thinking of heading out there. I just wanted to let you know when I would be there. **11:35 [andy](https://slack.com/archives/C08NFJSU753/p1757442907317149):** @Kevin **11:36 [Mason Radke](https://slack.com/archives/C08NFJSU753/p1757443010336219):** [[F09F5QUFGL8_powerflex_70_ec_node_192.168.102.76.dno]] [[F09ECSDHX6J_powerflex_70_ec_node_192.168.102.75.dno]] **11:37 [Mason Radke](https://slack.com/archives/C08NFJSU753/p1757443031337709):** i have these two files from the VFDs.. im hoping i saved them after everything was setup and working. **11:37 [Mason Radke](https://slack.com/archives/C08NFJSU753/p1757443050704289):** they may also only work with drive executive.. im not sure.. but here they are in case they are helpful **11:38 [andy](https://slack.com/archives/C08NFJSU753/p1757443124136459):** Cool thank you for those, I’ll check out the file type and see if they work with Ccsdww, the drive compared thing was very nice as a sanity check. It’s so funny when I learn things like that from other people like yourself and wonder what the hell they are doingat these paid automation fair conferences teaching stuff that nobody cares about. **11:38 [andy](https://slack.com/archives/C08NFJSU753/p1757443131496169):** CCW **11:39 [Mason Radke](https://slack.com/archives/C08NFJSU753/p1757443165407449):** book smart vs street smart **11:53 [Kevin](https://slack.com/archives/C08NFJSU753/p1757444034891209):** @andy do you need me there? **11:58 [andy](https://slack.com/archives/C08NFJSU753/p1757444293646219):** Being that we are trying to finish a bunch of stuff for Thursday I think it would be helpful to have you be able to focus on the VFD. Would you be able to meet me there this afternoon? **12:35 [Kevin](https://slack.com/archives/C08NFJSU753/p1757446537840479):** Ok I will be there around 2 **14:24 [Mason Radke](https://slack.com/archives/C08NFJSU753/p1757453053650759):** hows it going out there? **14:47 [andy](https://slack.com/archives/C08NFJSU753/p1757454424755829):** It looks like I got it to work regarding the well VFD by resetting the parameters to default, wiring the 24 V control circuit source voltage, downloading the program and rewiring the voltage. I got it to work in local hand and SCADA auto flow rate controlled. **14:48 [Mason Radke](https://slack.com/archives/C08NFJSU753/p1757454518724689):** oh wow. its working as we need it to?

Extracted Entities

TypeKeyValueConfidenceEvidence
contact Kevin Kevin 95% 11:03 [Kevin]
contact Mason Radke Mason Radke 95% 11:02 [Mason Radke]
contact andy andy 95% 11:09 [andy]
server PowerFlex 70 VFD IP 1 192.168.102.76 90% [[F09F5QUFGL8_powerflex_70_ec_node_192.168.102.76.dno]]
server PowerFlex 70 VFD IP 2 192.168.102.75 90% [[F09ECSDHX6J_powerflex_70_ec_node_192.168.102.75.dno]]
site Well 6 Well 6 80% i should be able to make some time to work on well 6
task Meet onsite to focus on VFD Kevin to meet Andy onsite around 2 PM to focus on VFD 90% Ok I will be there around 2
task Reset VFD and redownload program Reset VFD and redownload program to fix issues 85% I’m gonna try to reset the VFD and redownload the program
File: Clients/Tough/SMR/slack/2025/09/2025-09-09_tough-smr.md
Updated: 2026-02-20 02:20:21.542599