# #tough-smr — 2025-05-22
**17:14 [Kevin](https://slack.com/archives/C08NFJSU753/p1747959255319639):**
![[F08TL7Q93EH_20250522_170758.jpg]]
**17:15 [Kevin](https://slack.com/archives/C08NFJSU753/p1747959311367299):** Does wire 205 power anything other than the stratix and fiber switch? @andy
**17:15 [Kevin](https://slack.com/archives/C08NFJSU753/p1747959319468489):** @andy
**17:16 [Kevin](https://slack.com/archives/C08NFJSU753/p1747959362236799):** The CB is only 1 amp.
**17:39 [andy](https://slack.com/archives/C08NFJSU753/p1747960750132589):** It’s supposed to just be the Stratix
**17:39 [andy](https://slack.com/archives/C08NFJSU753/p1747960766414579):** I don’t remember what I tied in, probably another switch
**17:40 [andy](https://slack.com/archives/C08NFJSU753/p1747960811208869):** I looked up the power consumption and it could be 21 to 30 W which would mean that breaker is too small
**17:43 [andy](https://slack.com/archives/C08NFJSU753/p1747960999672449):** I honestly didn’t realize they pulled that much power
**17:43 [Mason Radke](https://slack.com/archives/C08NFJSU753/p1747961037168849):** At least we have an easy fix to the tripping!