← Tough

Clients/Tough/CCSD/slack/2025/08/2025-08-25_ccsd-water-ignition.md

slack
Source
1
Chunks
1
Entities
Doc
Type

Content

# #ccsd-water-ignition — 2025-08-25 **10:18 [andy](https://slack.com/archives/C08TVA84PD4/p1756142308655849):** I created N-207 and N-208 for WRF, 207 is AI's and 208 is DI's since there are too many. Those will be instantiated soon But you don't have to create those views as I asked you to do before. **11:28 [andy](https://slack.com/archives/C08TVA84PD4/p1756146481848339):** Figured out why the Opto 22 controller was loosing config, the voltage was too low for the volatile memory write and never sucessfully performed the write so under a power cycle it was cleared. I adjusted the power supply to the higher end of the 5V output and it survived a power cycle holding the configuration. **13:59 [Mason Radke](https://slack.com/archives/C08TVA84PD4/p1756155560259319):** Nice work. **13:59 [Mason Radke](https://slack.com/archives/C08TVA84PD4/p1756155566512349):** Sounds like a touchy little thing **14:05 [andy](https://slack.com/archives/C08TVA84PD4/p1756155918160339):** And it gave no notification that it didn't work, it gave notification that it successfully wrote to flash when it didn't. If you wanna break trust with the integrator that's how you do it. **16:12 [andy](https://slack.com/archives/C08TVA84PD4/p1756163522636709):** I took some screenshots on the actual iPad so you can see where it all fits before you replicate them. ![[F09BXUZJR6H_img_0103.png]] ![[F09CTEHUD4Y_img_0104.png]] ![[F09C39C1LAG_img_0105.png]] ![[F09BV172N3D_img_0106.png]] ![[F09BLHFMVHV_img_0107.png]] ![[F09BV15NAJX_img_0108.png]] ![[F09BZ7PHBFC_img_0109.png]] ![[F09C39D49AQ_img_0110.png]] ![[F09C1E4P3DL_img_0111.png]] ![[F09CTEKJKDE_img_0112.png]] **19:21 [Kevin](https://slack.com/archives/C08TVA84PD4/p1756174896512079):** I really like that you can see straight away where the faults are at just a glance. Nice work!

Extracted Entities

TypeKeyValueConfidenceEvidence
system controller product Opto 22 90% Figured out why the Opto 22 controller was loosing config
File: Clients/Tough/CCSD/slack/2025/08/2025-08-25_ccsd-water-ignition.md
Updated: 2026-02-20 02:20:27.172302