# RDT 7020 RDT 7020 12/3/2025 Troubleshoot analog signal to polymer. Poly system stays at zero speed when system turns on. Measured analog when system was running at Poly panel. showed 0ma Measured analog when system was running at 7020 panel. showed 0ma Adam had us test the output with Poly HOA in Hand. output still read 0ma Began the process of moving from analog output CH0 to CH2. Went online with the processor and enabled CH2 in the card configuration. set the clamping limits to 4000 and 20000. Found where the analog output is being written to in the program. Found the following: POLYMER- RUNG 12 program was telling the analog output to be 0 when HOA is off. confused because the settings of the analog card should clamp it at 4000. set source from 0 to 4000 and tested by putting physical hoa in hand then off. analog output is now reading 4ma. put hoa in hand analog output is now 7.5 ma testing the system again system worked. put the source from Rung 12 back to 0 and had Mychal turn the system off and back on again. system still worked. confused as to why the system is now working. seems possible that by changing the settings of the analog output card, it maybe re-wrote configurations to the card, thereby fixing some "glitch" in the card. Mychal put the system on and is running it to see how she does. for grins, I verified that the 7010 plc also writes 0 to the output when HOA is off It does.

Extracted Entities

TypeKeyValueConfidenceEvidence
contact Person Name Adam 80% Adam had us test the output with Poly HOA in Hand
contact Person Name Mychal 80% Mychal turn the system off and back on again
server Panel Name 7020 panel 90% Measured analog when system was running at 7020 panel
server Panel Name Poly panel 90% Measured analog when system was running at Poly panel
server PLC Name 7010 plc 80% verified that the 7010 plc also writes 0 to the output when HOA is off
site Client Name SSLOCSD 100% Client: SSLOCSD
task Troubleshooting Analog Signal Troubleshoot analog signal to polymer system 90% Troubleshoot analog signal to polymer. Poly system stays at zero speed