# CCT PLC PROGRAM NOTES
200204
ADDING NIGHT TIME PID LOOPS FOR BOTH CL2 AND BISUL
![[CCT_PLC_PROGRAM_NOTES_c5f92d27660e.png]]
![[CCT_PLC_PROGRAM_NOTES_44dceb98762a.png]]
![[CCT_PLC_PROGRAM_NOTES_cfdc2a5bee9e.png]]
![[CCT_PLC_PROGRAM_NOTES_b1eceacc7485.png]]
![[CCT_PLC_PROGRAM_NOTES_09523f782e5d.png]]
use deadband to allow a "range" of ORP, rather than a firm setpoint
CALCULATE BASELINE DOSAGE [ OR JUST ENTER A BASELINE PUMP OUTPUT ]
SET PUMP OUTPUT TO FEED THAT DOSAGE
WAIT
INCREASE OR DECREASE OUTPUT BY Z% AFTER Xsec
WHEN THE PV IS WITHIN Y% OF SP, ENABLE PID
IF THE PV IS OUTSIDE OF Y% FOR Xmin ADD OR SUBTRACT BIAS
ETHERNET I/P I/O ASSIGNMENTS FOR E+H UNITS
AI1=AE-110a ORP mV
AI2=AE-110a TEMP DEG C.
AI3=AE-110b ORP mV
AI4=AE-110B TEMP DEG C
DI1=ALARM RELAY