# SCADA IMPROVEMENTS PROPOSAL
SCADA LICENSE UPGRADE?
CHANGES TO ORIGINAL ASSESSMENT BY THE DISTRICT:
CENTRIFUGE
MIMIC ALL SCREENS FROM HMI IN SCADA (THIS WILL INCREASE THE SCREEN COUNT UNLESS WE CONDENSE IT DOWN TO 1 OR 2 SCREENS)
INFLUENT PUMPS
MIMIC ALL SCREENS FROM HMI IN SCADA
CCT
ADD CONTROLS FOR THE EFFLUENT PUMPS
ADD SPEED AND CONTROL FOR CHEMICAL PUMPS
ADD BACKUP CHEM SYSTEMS ON/OFF INDICATOR AND ALARM
ADD BACKUP CHEM SYSTEM PV SETPOINT
GRIT KING
ADD ANALOG OUTPUT FOR FERRIC PUMP DOSE CONTROL
ADD FERRIC PUMP RUNNING SIGNAL
ADD MODBUS COMM TO THE PLC
ADD MANUAL START/STOP
ADD RUN CYCLE SETPOINTS AND CYCLE TIMER DISPLAY
PRIMARY CLARIFIERS
ADD SLUDGE PUMP SPEED AND TIMING SETTINGS (FROM NEW CONTROLS IN NEW MCC PLC)
FFR
ADD PERIPHERAL DRIVE SPEED DISPLAY AND CONTROL (REPLACE DRIVE??)
HEATING / MIXING
ADD POLYMER PUMP RATE CONTROL
DIGESTERS
ADD DIGESTER LEVEL PRI & SEC
ADD DIGESTER GAS FLOW PRI & SEC
FLARE
ADD GAS PRESSURE
RECLAIMED WATER
ADD AMIAD FILTER FLUSH COUNT
ADD AMIAD FILTER MANUAL FLUSH AND COUNTER RESET
COSTING NOTES:
CENTRIFUGE-
INCLUDE LABOR TO CREATE A NEW SCREEN RATHER THAN DOING AN IMPORT
GRIT KING-
ADD COST OF THE PLC SOFTWARE