Estimated flow rates (by the District)
RECLAIM WATER PUMPS 150-300 GPM
SECONDARY DIGESTER SUMP PUMPS 80 GPM EACH
FLARE GAS TYPICAL FLOW 3000-4500 SCFH (50-75 SCFM) 10inwc max 97-98 degF
PRIMARY CLARIFIER PUMPS 160 GPM (MAX DIGESTER INFLOW 220 GPM + DRUM THICKENER FLOW)
HOT WATER PUMP 130 GPM
HEATED SLUDGE PUMP (GUESSTIMATE 500 GPM)
WASTE SLUDGE PUMPS 110 GPM EACH (TYPICALLY RUN AT HALF THAT)
Influent pumps
Pressure sensor install
![[SCADA_project_instrument_spec_field_notes_img_20201201_101636.411.jpg]]
Should we add seal water pressure?
![[SCADA_project_instrument_spec_field_notes_img_20201201_102004.838.jpg]]
![[SCADA_project_instrument_spec_field_notes_img_20201201_101906.799.jpg]]
![[SCADA_project_instrument_spec_field_notes_img_20201201_101752.586.jpg]]
![[SCADA_project_instrument_spec_field_notes_img_20201201_102301.955.jpg]]
2 pumps 41 11/16 circumference
2 pumps 48 9/16
FFR
100 1/2 inch circ (calc'd 32" diam)
Probably better to weld a weldlet
![[SCADA_project_instrument_spec_field_notes_img_20201201_112210.992.jpg]]
Pump discharge psi is 4 psi
![[SCADA_project_instrument_spec_field_notes_img_20201201_112802.710.jpg]]
![[SCADA_project_instrument_spec_field_notes_img_20201201_112627.666.jpg]]
![[SCADA_project_instrument_spec_field_notes_img_20201201_112521.249.jpg]]
![[SCADA_project_instrument_spec_field_notes_img_20201201_113349.885.jpg]]
Primary clarifies
![[SCADA_project_instrument_spec_field_notes_img_20201201_113628.556.jpg]]
![[SCADA_project_instrument_spec_field_notes_img_20201201_113609.248.jpg]]
Looks like we will have to mount the sensor inside and be intrinsically safe.
Flow meter. Need to find a spot where both clarifier pumps pump through to get into the digester. The line in the video may work.
Digester gas pressure is 30 inches water on compressor discharge and 3 inwc on suction. Compressor is currently off. Check to see if they still want to monitor it.
H/M PLC
![[SCADA_project_instrument_spec_field_notes_img_20201201_121910.759.jpg]]
![[SCADA_project_instrument_spec_field_notes_img_20201201_121848.388.jpg]]
Digester WAS line is 6 inch
![[SCADA_project_instrument_spec_field_notes_img_20201201_122054.753.jpg]]
Heated sludge return line is 4inch stainless
![[SCADA_project_instrument_spec_field_notes_img_20201201_122151.015.jpg]]
Heated sludge pump is 8.85 FLA
![[SCADA_project_instrument_spec_field_notes_img_20201201_122302.846.jpg]]
Mixing pump discharge psi is 5
hot water line is 3 inch steel
Digester gas line inside H/M is 2 inch stainless
Heated sludge discharge psi is 22 psi
Hot water psi is variable. Gages are 0 to 100
There are temp sensors existing for heated sludge exchanger input and output.
Max hot water temp is 150 degF
![[SCADA_project_instrument_spec_field_notes_img_20201201_122530.705.jpg]]
![[SCADA_project_instrument_spec_field_notes_img_20201201_122443.534.jpg]]
![[SCADA_project_instrument_spec_field_notes_img_20201201_122434.058.jpg]]
![[SCADA_project_instrument_spec_field_notes_img_20201201_122403.053.jpg]]
![[SCADA_project_instrument_spec_field_notes_Snapshot_10.jpg]]
![[SCADA_project_instrument_spec_field_notes_Snapshot_7.jpg]]
![[SCADA_project_instrument_spec_field_notes_Snapshot_6.jpg]]
![[SCADA_project_instrument_spec_field_notes_Snapshot_11.jpg]]
![[SCADA_project_instrument_spec_field_notes_Snapshot_9.jpg]]
![[SCADA_project_instrument_spec_field_notes_Snapshot_8.jpg]]
Secondary sludge pump discharge is 6 inch ductile
![[SCADA_project_instrument_spec_field_notes_img_20201201_133704.171.jpg]]
Gas flare line is 4 inch pvc
Gas pressure is 4 inwc
![[SCADA_project_instrument_spec_field_notes_img_20201201_134150.739.jpg]]
![[SCADA_project_instrument_spec_field_notes_img_20201201_134117.781.jpg]]
MCC/CCT PLC
![[SCADA_project_instrument_spec_field_notes_img_20201201_134937.387.jpg]]
![[SCADA_project_instrument_spec_field_notes_img_20201201_134932.792.jpg]]
Extracted Entities
| Type | Key | Value | Confidence | Evidence |
| site |
Client Name |
SSLOCSD |
100% |
Client: SSLOCSD |
File: Clients/SSLOCSD/evernote/SCADA_project_instrument_spec_field_notes.md
Updated: 2026-02-19 22:10:09.538502