# #paso-ob1-boost — 2026-01-21 **01:35 [andy](https://slack.com/archives/C0A4JNJ8B7S/p1768988159552659):** I know I'm typing into the void but the program won't call the pumps. I wish this was normal business hours cuz I can't figure out how to get LLS to call a pump and we don't go home until it does. **02:19 [Mason Radke](https://slack.com/archives/C0A4JNJ8B7S/p1768990768232869):** I woke up and was just setting my alarm **02:20 [Mason Radke](https://slack.com/archives/C0A4JNJ8B7S/p1768990811626779):** Make sure it's in program mode **02:20 [Mason Radke](https://slack.com/archives/C0A4JNJ8B7S/p1768990832604069):** Logic should be all set to run the LLS and call pumps **02:21 [Mason Radke](https://slack.com/archives/C0A4JNJ8B7S/p1768990878622409):** LLS probably has some cfg preventing the call? **02:28 [Mason Radke](https://slack.com/archives/C0A4JNJ8B7S/p1768991320149379):** If you have to open up the AOI logic, find the pump call outputs and see what tags are not true that are holding it up. I had the LLS calling for pumps and working in sim. Guessing it's a mode or something in the LLS. If you have factory talk ME installed you could make an empty page with the LLS object and check the faceplate for status and configuration **03:16 [andy](https://slack.com/archives/C0A4JNJ8B7S/p1768994187186849):** I just wrote some basic code to get us heading home but I need to correct it tomorrow. Thanks for responding, didn’t expect that! **14:40 [andy](https://slack.com/archives/C0A4JNJ8B7S/p1769035221841159):** Mason, your reputation remains unbesmerged, when not in Sim mode; my custom code interferes with the start and stop commands in a motor and vsd object. When I removed them, the motors worked right. **14:41 [Mason Radke](https://slack.com/archives/C0A4JNJ8B7S/p1769035276943169):** Got it working? **14:41 [andy](https://slack.com/archives/C0A4JNJ8B7S/p1769035282018409):** Yep **14:45 [Mason Radke](https://slack.com/archives/C0A4JNJ8B7S/p1769035528557209):** :raised_hands: **16:37 [andy](https://slack.com/archives/C0A4JNJ8B7S/p1769042271156849):** The LLS program keeps kicking into Oper mode and stopped running spontaneously and the fire pump ran **16:38 [andy](https://slack.com/archives/C0A4JNJ8B7S/p1769042291950049):** I'm on hold waiting for support, any ideas why that might be happening? **16:38 [Mason Radke](https://slack.com/archives/C0A4JNJ8B7S/p1769042311651379):** Fire pump will only run on set points. Pressure must have dropped? **16:40 [andy](https://slack.com/archives/C0A4JNJ8B7S/p1769042439579569):** Pressure dropped because LLs never called pulls **16:40 [andy](https://slack.com/archives/C0A4JNJ8B7S/p1769042440698749):** Pumps **16:41 [andy](https://slack.com/archives/C0A4JNJ8B7S/p1769042487775019):** We were just sitting bull shitting and then the LLS didn't call pumps and pressure dropped fire pump turned on and I noticed Oper mode, forced it back into Prog mode and it ran **16:42 [andy](https://slack.com/archives/C0A4JNJ8B7S/p1769042535918559):** I noticed it switched back automatically to Oper while I was waiting for pressure to drop. No changes in field signals

Extracted Entities

TypeKeyValueConfidenceEvidence
system FactoryTalk ME FactoryTalk ME 90% If you have factory talk ME installed you could make an empty page
File: Clients/Tough/Paso-Boosters/slack/2026/01/2026-01-21_paso-ob1-boost.md
Updated: 2026-02-23 17:00:16.308696