# Buellton SCADA Proposal I/O Points Reservoir 3=5 | 121 | Battery Volts | 25.54 Volts | 2012-03-06 06:03:00 | | | | --- | --- | --- | --- | --- | --- | | 122 | 5 Volt Supply Reading | 4.91 Volts | 2012-03-06 05:59:38 | | | | 125 | Battery Volts Open | 0 | 2012-03-06 05:59:07 | | | | 126 | 5 Volt Supply Open | 0 | 2012-03-06 05:59:01 | | | | 2001 | RES3_DI-1_DOOR_CLOSED | 1 | 2012-03-06 05:59:53 | | | | 2002 | RES3_DI-2_CTR_DOOR_OK | 0 | 2012-03-06 05:59:20 | | | | 2003 | RES3_DI-3_SIDE_DOOR_OK | 1 | 2012-03-06 06:30:10 | | | | 2037 | RES3_AI-1_LVL | 11.35 Ft | | | | Res 3 Booster = 23 | 121 | Battery Volts | 27.34 Volts | 2012-03-06 06:00:59 | | | | --- | --- | --- | --- | --- | --- | | 122 | 5 Volt Supply Reading | 4.94 Volts | 2012-03-06 06:29:49 | | | | 125 | Battery Volts Open | 0 | 2012-03-06 06:29:49 | | | | 126 | 5 Volt Supply Open | 0 | 2012-03-06 06:30:15 | | | | 2001 | BS_DI-1_DOOR_CLOSED | 1 | 2012-03-06 06:35:40 | | | | 2002 | NEW_BS_DI-2_DOOR_CLOSED | 0 | 2012-03-06 06:29:54 | | | | 2003 | NEW_BS_DI-3_P1_FAIL | 0 | 2012-03-06 06:30:01 | | | | 2004 | NEW_BS_DI-4_P2_FAIL | 0 | 2012-03-06 06:30:32 | | | | 2005 | NEW_BS_DI-5_OFFLINE | 0 | 2012-03-06 06:30:25 | | | | 2006 | OLD_BS_DI-6_OFFLINE | 1 | 2012-03-06 06:30:04 | | | | 2007 | NEW_BS_DI-7_START_CK | 1 | 2012-03-06 06:03:30 | | | | 2008 | OLD_BS_DI-8_START_CK | 1 | 2012-03-06 06:29:54 | | | | 2009 | OLD_BS_DI-9_RUN | 0 | 2012-03-06 06:29:47 | | | | 2010 | OLD_BS_DI-10_BACKFLO | 1 | 2012-03-06 06:30:13 | | | | 2011 | NEW_BS_DI-11_HI_TEMP | 0 | 2012-03-06 06:29:57 | | | | 2012 | NEW_BS_DI-12_CTLR_ALM_OK | 1 | 2012-03-06 06:31:05 | | | | 2013 | NEW_BS_DI-13_RUN | 0 | 2012-03-06 06:29:59 | | | | 2017 | OLD_B_DI-17_PUMP_FAIL | 0 | 2012-03-06 06:29:59 | | | | 2018 | NEW_B-1_DI-18_PUMP_FAIL | 0 | 2012-03-06 06:30:30 | | | | 2019 | NEW_B-2_DI-19_PUMP_FAIL | 0 | 2012-03-06 06:30:23 | | | | 2021 | NEW_BS_DO-1_START | 0 | 2012-03-06 03:03:23 | | | | 2022 | OLD_BS_DO-2_START | 0 | 2012-02-17 14:17:44 | | | | 2072 | NEW_BS_DO-20_PWR_CYC_SIU | 0 | 2012-02-17 14:22:46 | | | | 2077 | NEW_BS_DV-1_START_Verify | 0 | 2012-03-06 06:03:32 | | | | 2078 | OLD_BS_DV-2_START_Verify | 0 | | | | Reservoir 1 & 2 / W9 = 20 | 121 | Battery Volts | 27.37 Volts | 2012-03-06 06:05:49 | | | | --- | --- | --- | --- | --- | --- | | 122 | 5 Volt Supply Reading | 4.92 Volts | 2012-03-06 06:49:19 | | | | 125 | Battery Volts Open | 0 | 2012-03-06 06:48:53 | | | | 126 | 5 Volt Supply Open | 0 | 2012-03-06 06:48:52 | | | | 2001 | RES12_DI-1_SP_DOOR_CLOSED | 1 | 2012-03-06 06:48:49 | | | | 2002 | RES1_DI-2_DOOR_CLOSED | 1 | 2012-03-06 06:49:11 | | | | 2003 | RES2_DI-3_DOOR_CLOSED | 1 | 2012-03-06 06:48:31 | | | | 2004 | RES12_DI-4_W9_SP_DOOR_CLSD | 1 | 2012-03-06 06:48:34 | | | | 2005 | RES12_DI-5_W9_RECLAIM_HI | 0 | 2012-03-06 05:58:41 | | | | 2006 | RES12_DI-6_W9_BACKWASH_INHIBIT | 0 | 2012-03-06 05:58:36 | | | | 2007 | RES12_DI-7_W9_LOW_AIR_PSI | 0 | 2012-03-06 06:18:24 | | | | 2008 | RES12_DI-8W9_COMMON_ALM | 0 | 2012-03-06 06:35:58 | | | | 2009 | RES12_DI-9_W9_PURGE | 0 | 2012-03-06 06:13:47 | | | | 2010 | RES12_DI-10_W9_FILTRATION | 0 | 2012-03-06 06:52:12 | | | | 2011 | RES12_DI-11_W9_BACKWASH | 0 | 2012-03-06 05:56:42 | | | | 2012 | RES12_DI-12_W9_RECLAIM | 0 | 2012-03-06 06:48:49 | | | | 2013 | RES12_DI-13_W9_BW_TANK_FULL | 0 | 2012-03-06 06:53:16 | | | | 2014 | RES12_DI-14_W9_RECLAIM_READY | 0 | 2012-03-06 06:49:09 | | | | 2015 | RES12_DI-15_W9_PUMP_RUN | 0 | 2012-03-06 06:49:01 | | | | 2021 | RES12_DO-1_W9_CALL | 0 | 2012-03-06 00:51:49 | | | | 2037 | RES12_AI-1_LEVEL | 6.33 Ft | | | | McMurray WTP = 25 | 121 | Battery Volts | 27.27 Volts | 2012-03-06 06:21:10 | | | | --- | --- | --- | --- | --- | --- | | 122 | 5 Volt Supply Reading | 4.91 Volts | 2012-03-06 06:20:51 | | | | 125 | Battery Volts Open | 0 | 2012-03-06 06:20:51 | | | | 126 | 5 Volt Supply Open | 0 | 2012-03-06 06:21:05 | | | | 2001 | MCM_DI-1_DOOR_CLOSED | 1 | 2012-03-06 06:32:09 | | | | 2002 | MCM_DI-2_Reclaim_Hi_Level | 0 | 2012-03-06 06:20:48 | | | | 2003 | MCM_DI-3_Backwash_Inhibit | 0 | 2012-03-06 06:21:02 | | | | 2004 | MCM_DI-4_Low_Air_Pressure | 0 | 2012-03-06 06:35:46 | | | | 2005 | MCM_DI-5_Common_Alarm | 0 | 2012-03-06 06:20:59 | | | | 2006 | MCM_Filter_A_DI-6_Purge_Run | 0 | 2012-03-06 06:53:22 | | | | 2007 | MCM_Filter_A_DI-7_Run | 0 | 2012-03-06 06:15:51 | | | | 2008 | MCM_Filter_A_DI-8_Backwash_Run | 0 | 2012-03-06 06:20:13 | | | | 2009 | MCM_Filter_B_DI-9_Purge_Run | 0 | 2012-03-06 06:20:33 | | | | 2010 | MCM_Filter_B_DI-10_Run | 0 | 2012-03-06 06:49:05 | | | | 2011 | MCM_FilterB_DI-11_Backwash_Run | 0 | 2012-03-06 06:55:20 | | | | 2012 | MCM_DI-12_Reclaim_Run | 0 | 2012-03-06 06:20:53 | | | | 2013 | MCM_DI-13_Backwash_Tank_Full | 0 | 2012-03-06 06:21:09 | | | | 2014 | MCM_DI-14_Reclaim_Ready | 0 | 2012-03-06 06:20:52 | | | | 2015 | MCM_DI-15_Rmt_Call_Well3 | 0 | 2012-03-06 05:56:31 | | | | 2016 | MCM_DI-16_Rmt_Call_Well7 | 0 | 2012-03-06 06:49:09 | | | | 2017 | MCM_DI-17_Rmt_Call_Well8 | 0 | 2012-03-06 06:15:53 | | | | 2018 | MCM_DI-18_WELL3_COM_FAIL | 0 | 2012-03-06 06:26:21 | | | | 2019 | MCM_DI-19_WELL7_COM_FAIL | 0 | 2012-03-06 06:21:03 | | | | 2020 | MCM_DI-20_WELL8_COM_FAIL | 0 | 2012-03-06 06:34:44 | | | | 2021 | MCM_DO-1_Call_Filter_A | 0 | 2012-02-17 09:11:52 | | | | 2022 | MCM_DO-2_Call_Filter_B | 0 | | | | Scope: Install radios at Res 3, Booster, McMurray Use a ethernet serial server between the SCADA PC and the radio at the office. Install PC, radio, ethernet/serial server, and power supply at the office. Steps: 1) Equipment Install 2) Establish Comm 3) Configure SCADA 4) Program Booster to talk to Res 3 for level control 5) Cut over Res 3 and Booster to new SCADA 6) Program Well 9 for control and comm with Res 1/2 7) Program McMurray for control and comm with Res 1/2 8) Cut over Res 1/2, Well 9, and McMurray

Extracted Entities

TypeKeyValueConfidenceEvidence
site Client Plant Buellton 100% Client: Buellton
site Res 3 Booster Res 3 Booster 100% Res 3 Booster = 23
site Reservoir 1 & 2 / W9 Reservoir 1 & 2 / W9 100% Reservoir 1 & 2 / W9 = 20
site McMurray WTP McMurray WTP 100% McMurray WTP = 25
site Reservoir 3 Reservoir 3 100% Reservoir 3=5
system SCADA System SCADA PC 90% Use a ethernet serial server between the SCADA PC and the radio
task Program Well 9 Program Well 9 for control and comm with Res 1/2 90% 6) Program Well 9 for control and comm with Res 1/2
task Program McMurray Program McMurray for control and comm with Res 1/2 90% 7) Program McMurray for control and comm with Res 1/2
task Cut over Res 1/2, Well 9, and McMurray Cut over Res 1/2, Well 9, and McMurray 90% 8) Cut over Res 1/2, Well 9, and McMurray
task Equipment Install Install radios at Res 3, Booster, McMurray; install PC, radio, ethernet/serial server, and power supply at the office 90% Install radios at Res 3, Booster, McMurray; Install PC, radio, ethernet/serial server
task Establish Comm Establish communication between devices 90% 2) Establish Comm
task Configure SCADA Configure SCADA system 90% 3) Configure SCADA
task Program Booster Program Booster to talk to Res 3 for level control 90% 4) Program Booster to talk to Res 3 for level control
task Cut over Res 3 and Booster Cut over Res 3 and Booster to new SCADA 90% 5) Cut over Res 3 and Booster to new SCADA