# RAS PIT I/O Modbus Moxa Modular IO Admin Software: https://cdn-cms.azureedge.net/getmedia/0f6e50fe-6a4c-4ea5-9f3b-8454c373b751/moxa-iologik-4000-series-iologik-e4200-modular-ioadmin-configuration-utility-v1.6.1.zip - add the adapter ![[Screenshot 2024-07-09 at 10.40.55 AM.png]] - login under the Adapter Settings tab.  the password is blank.. hit login. ![[Screenshot 2024-07-09 at 10.41.07 AM.png]] - the modules will automatically load at this point. ![[Screenshot 2024-07-09 at 10.41.16 AM.png]] - select the IO module and then the modbus address tab.  the address is listed in Hex.  0x0800 for example = 2048 which indicates a modbus address of 32048.  In Clear Scada we shift this by 1, so the final address in scada is 32049 ![[Screenshot 2024-07-09 at 10.41.24 AM.png]]