← Buellton

Clients/Buellton/evernote/Scada_work_log.md

evernote
Source
1
Chunks
11
Entities
Doc
Type

Content

# Scada work log 220621 Lift 1 PLC has been locking up. Comms go out then come back. Had Joe check yesterday and there was a fault light on the PLC that he cleared with a power cycle, but comms didn't come back until after 6pm. Radio is showing a RF power alarm off and on. Maybe time for a new antenna. 220618 Configured pump runtime alarms for Lift stations. 220204 New internet router was installed at the wwtp. Had to setup port forwarding. Notes on how in the scada network note. 200817 Windows firewall was blocking the OPC communication to the PLCs. Not sure how this happened. There were a couple power outages that outlasted the UPS. I had to set the network to Private  [https://social.technet.microsoft.com/Forums/windowsserver/en-US/98f41513-df6f-4065-975a-6d6dc2308a94/server-2012-r2-change-network-location-from-public-to-private](https://social.technet.microsoft.com/Forums/windowsserver/en-US/98f41513-df6f-4065-975a-6d6dc2308a94/server-2012-r2-change-network-location-from-public-to-private)  and then add ports 44818 and 2222 to incoming and outgoing rules First entry 180828 Added Zaca IO to scada database Modified all user accounts to auto logout after 5 min Added starts and runtimes to Lift 1 database None of the runtimes or starts are reporting 180912 DELETED OLD SNAPSHOTS OF VM AND CREATED A NEW ONE INSTALLED WINDOWS UPDATES MANUALLY BACKED UP THE DATABASE  INSTALLED CLEARSCADA UPDATE 2017R2 HAD TO INSTALL THE MOBILE SERVER SEPARATELY HAD TO GO BACK TO CLEARSCADA SETUP AND INSTALL THE MOBILE COMPANION SERVER HAD TO CHANGE THE PORT BINDING FROM 443 TO 444 IN IIS AND THEN START THE WEBSITE 180925 WORKING ON MOBILE CONNECTIONS FAULT WORKING ON BACKUP OPERATION FAULT SET WINDOWS FIREWALL ON FOR PUBLIC AND PRIVATE CONNECTIONS. THERE HAVE BEEN SOME EVENT ENTRIES THAT SHOW BAD ACCESS ATTEMPTS FROM \$ROOT. NOT SURE IF THIS IS MALICIOUS. ADDED INBOUND RULE FOR SSH PORTS 444 AND 445 181103 ADDING RES3 BOOST TAGS TO OPC ADDED A SysNotice email (my email) USER AND SET REDIRECT OF OPC SCANNER OBJECT TO REDIRECT TO IT ON ANY CHANGE. IF THE OPC SERVER IS OFFLINE FOR MORE THAN 10 MIN THEN IT WILL REDIRECT TO SysAlarm email (my phone) 181115 Added the needed registers to the Res1 plc comm to the booster.  Added L2TP VPN to router 181218 Added user JeremyL jeremy1234  Added sewer on all phone pin 1470

Extracted Entities

TypeKeyValueConfidenceEvidence
contact SysNotice Email my email 70% ADDED A SysNotice email (my email) USER
contact SysAlarm Phone my phone 70% SysAlarm email (my phone)
credential User Credential username: JeremyL / password: jeremy1234 95% Added user JeremyL jeremy1234
credential Phone PIN 1470 90% Added sewer on all phone pin 1470
server IIS Port Binding 444 90% HAD TO CHANGE THE PORT BINDING FROM 443 TO 444 IN IIS
server Windows Firewall Ports 44818, 2222 90% add ports 44818 and 2222 to incoming and outgoing rules
server SSH Ports 444, 445 90% ADDED INBOUND RULE FOR SSH PORTS 444 AND 445
site Client Name Buellton 100% Client: Buellton
system SCADA Product ClearSCADA 2017R2 95% INSTALLED CLEARSCADA UPDATE 2017R2
system Mobile Server ClearSCADA Mobile Server and Mobile Companion Server 90% HAD TO INSTALL THE MOBILE SERVER SEPARATELY ... MOBILE COMPANION SERVER
vpn VPN Type L2TP VPN 90% Added L2TP VPN to router
File: Clients/Buellton/evernote/Scada_work_log.md
Updated: 2026-02-25 05:50:08.382814