# Untitled Note RWPS VFD DESIGN REVIEW NOTES - MISSING HIGH SPEED FUSES- MISSING MOTOR HEATER ON PILOT LIGHT- MISSING DOOR MOUNTED ETM CAN WE ASK FOR ALL VFD CONTROL TERMINALS TO BE WIRED TO TERMINAL BLOCKS? THEY SAY ALL FIELD WIRING MUST LAND ON TERMINAL BLOCKS.