# 02/29/12 RW pumps not going to full pressure - Need to add setpoint to RWPS screen for adjusting the switch over flow setting- Pump 8120 won't start Pump 8120 was in off. Switched to off 8120 would not start in auto or hand from scada. Found the wrong address on line 45 LAD 13. Pressure PID output is at 100% but pump speed is 90% Pump8130 AUTO STATUS B10:33/12 IS OFF The Pv is out of scale in the PID loop PIT-8100 scale is 0-120. I had set the high scale of the PID block to 150 thus throwing the PV scaling off. Changed the high scale back to 120 Set the Max value allowed to be entered in scads to 120 to fix the pid error from the other night