# Andante Mods 180910 Problem: When the power goes out the pumps won't restart in auto until the PLC is reset Fix: Removed NO contact C113 from line 70 and NC on line 67 Removed NO contact C114 from line 72 and line NC from line 68 181025 Loaded the revision and tested it by simulating a power outage and changing setpoints before simulating the outage so both pumps and the high alarm would trigger when the power returned. The high level alarm and the pumps came on when power was restored.