# Country club RW submittal review notes Cla-Val submittal- Contractor to provide options C, M, P, S - which includes the X144 E-FLOW METER as required in specifications- Change the VC-22D enclosures to "IP-65" type with conduit connections- Contractor to provide "Modbus TCP / Ethernet" communications option for VC-22D Valve Controllers 8" Flow Meter submittal - Contractor to provide the model number of the UltraMag flow meter. Note, to be considered as an approved equal, we are looking for these options: Ultra Mag with ProComm Converter, Meter mount converter, DC Power, Modbus + STD outputs- Contractor to provide and install grounding rings with the meter per plan.