# UF upgrade design
Meeting with Reza at Veolia
Check with Thompson on:
MCC material. Powder Coated ok?
MCC location has changed, will require rerouting of conduit and repulling of conductors, or a splice box possibly
Figure out what conduits will need to be rerouted.
![[UF_upgrade_design_Snapshot.png]]
11/14/24
Review of Veolia submittal
Questions:
-
What make/model is the PLC/HMI - found reference to an obsolete HMI in 3.2 of the control philosophy 5580 CONTROLOGIX WITH 3MB, PANELVIEW PLUS 7 15"-
Is there a UPS? YES-
We will determine the IP addresses (EN13-DN-001 Note 3) (See pics below)
![[UF_upgrade_design_image.png]]
-
Can the B-85 and AC-91A be powered by a soft-starter (RVSS)?-
Add fuses for each digital output wired directly to solenoids and valves (T03-0330-DI-001 sht 17,18)-
Add fuses for each analog input and output (sht,19-
Add fuses for each switch that is outside of the control cabinet connected directly to digital inputs-
Are the Process pump motors inverter duty rated? No motor part number was provided (BOM pg10)-
Did we decide to not add the chemical flow meters? I had suggested it in my first review. I remember talking about it in the meeting, but don't remember the outcome.-
Change MagMeter Proline 400 transmitter from aluminum housing to polycarbonate-
Wire both analog signal (flow rate) and digital pulse signal (100 gal pulse) from MagMeters to PLC. Use digital pulse signal for the flow totalizer in the PLC.-