Perfect. Sounds like a plan! I'm fairly certain both NICs on the PLC share the same internal microcontroller so regarding overall throughput I'm not certain that would improve things. However this fiber line that connects CP4000 to the rest of the network; does it use Media converters/SFP Modules? It may be that the SFP modules are unmatched/faililng/not the correct wavelength or fiber line is kinked somewhere. Just to rule it out completely I would do a throughput test on each side of that fiber run, possibly use an OTDR to see if there is any signal loss or leakage happening in the specific fiber strand. You can call me whenever you'd like to discuss. *Chad Crawford* *Chief Technical Officer* SPICE Integration *805.464.4111* C-10 License: *1110179* California Small Business Certification ID: *2036507* On Thu, Feb 26, 2026 at 1:01 PM Kevin Seifert <kevin@autosysnet.com> wrote: > Mason and I are out here now doing the leg work to document the current > SCADA/PLC network here in the new side of the plant called CP4000. > [... earlier replies trimmed ...]