Perfect. Sounds like a plan! I'm fairly certain both NICs on the PLC share
the same internal microcontroller so regarding overall throughput I'm not
certain that would improve things. However this fiber line that connects
CP4000 to the rest of the network; does it use Media converters/SFP
Modules? It may be that the SFP modules are unmatched/faililng/not the
correct wavelength or fiber line is kinked somewhere. Just to rule it out
completely I would do a throughput test on each side of that fiber run,
possibly use an OTDR to see if there is any signal loss or leakage
happening in the specific fiber strand.
You can call me whenever you'd like to discuss.
*Chad Crawford*
*Chief Technical Officer*
SPICE Integration
*805.464.4111*
C-10 License: *1110179*
California Small Business Certification ID: *2036507*
On Thu, Feb 26, 2026 at 1:01 PM Kevin Seifert <kevin@autosysnet.com> wrote:
> Mason and I are out here now doing the leg work to document the current
> SCADA/PLC network here in the new side of the plant called CP4000.
>