# #paso-24th-boost — 2026-03-02
**08:27 [Mason Radke](https://slack.com/archives/C0AGE36Q0P5/p1772468856301559):** @andy so there was not a lot of work needed on this one. let me know if I missed anything: I have MT101 and MT102 on a LLS object to control lead lag and alternation functions.. MT103 (fire pump) outside of the LLS with its own set of start /stop setpoints. everything else remained the same.. such as low pressure switches, etc
**08:29 [Mason Radke](https://slack.com/archives/C0AGE36Q0P5/p1772468961816609):** i also updated the demand call logic to only use the 2 pumps instead of 3
**09:05 [andy](https://slack.com/archives/C0AGE36Q0P5/p1772471110771409):** Right, that makes sense to me. I'll update ignition object references to match your changes. Thank you!
**09:06 [Mason Radke](https://slack.com/archives/C0AGE36Q0P5/p1772471193692209):** if you want i can gather the setpoint tags and give you a list of what is what (they have comments in code, but if its helpful to have them compiled let me know)
**12:39 [andy](https://slack.com/archives/C0AGE36Q0P5/p1772483973249059):** Yes please compile the list
**17:42 [Mason Radke](https://slack.com/archives/C0AGE36Q0P5/p1772502148778859):**
Here's the PC100 Pump Controller Setpoint tag structure for reference:
PC100.Setpoints
PC100.Setpoints[0] — Lead Pump Start
PC100.Setpoints[1] — Lead Pump Stop
PC100.Setpoints[2] — Lag Pump Start
PC100.Setpoints[3] — Lag Pump Stop
PC100.Setpoints[4] — Fire Pump Start
PC100.Setpoints[5] — Fire Pump Stop