**10:38 [Kevin](https://slack.com/archives/C09D358F91R/p1772822298637069):** I'm connecting the Bonita Well hopefully. Are you available to assist with testing?
**10:38 [Kevin](https://slack.com/archives/C09D358F91R/p1772822303830069):** @Mason Radke
**10:51 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772823092576129):** Not really, but let me know.
**10:51 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772823098088749):** I can connect if you need help
**10:59 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772823553648189):** Let me know when you get things set up and I can get connected to try and test
**10:59 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772823567997119):** Im out on the Carrizo Plains
**11:57 [Kevin](https://slack.com/archives/C09D358F91R/p1772827074335839):** I just connected the radio and board but still show comm fail on SCADA. I think I need to change the board address. Trying to find where I put that information
**11:58 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772827138918619):** I wouldn’t trust comm fail on scada
**11:59 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772827166514459):** Ask Otto Bot. It has the RF scsda manual.
**12:03 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772827402599849):** @AutoBot how do you change the address on an rfscada board?
**12:03 [AutoBot](https://slack.com/archives/C09D358F91R/p1772827404676879):** :mag: Searching the vault…
**12:03 [AutoBot](https://slack.com/archives/C09D358F91R/p1772827409680139):**
To change the Modbus address on an RFScada board, you need to write the desired Modbus address value to register 611. The valid range for the user Modbus address is from 1 to 98 or 100 to 255. The default address is 0 (off). Note that the RFScada units will always respond to address 99 (0x63 Hex) regardless of the user-set address, which allows access even if the user address is zero or lost.
Summary:
- Register for Modbus address: 611
- Valid address range: 1 to 98 or 100 to 255
- Default: 0 (off)
- Address 99 is always active for access
(Source: vault_files/F0A78KW8QRK_Modbus_section_from_RFScada4_16Manual.pdf and Reference/Manuals/RFScada/Modbus_section_from_RFScada4_16Manual.pdf)
:card_file_box: *Sources* (10 chunks):
• `vault_files/F0A78KW8QRK_Modbus_section_from_RFScada4_16Manual.pdf`
• *Reference* — `Reference/Manuals/RFScada/Modbus_section_from_RFScada4_16Manual.pdf`
• *Rancho-Ynecita* — `Clients/Rancho-Ynecita/remarkable/RFScada_Board_Modbus_comms_for_Ynecita_-_Sheet1.pdf`
• *Rancho-Ynecita* — `Clients/Rancho-Ynecita/slack/2026/01/2026-01-02_rancho-ynecita.md`
**12:20 [Kevin](https://slack.com/archives/C09D358F91R/p1772828448125509):** The board unit ID is in register 608
**12:21 [Kevin](https://slack.com/archives/C09D358F91R/p1772828481035369):** It appears that I have the Bonita board set correct at unit ID 3.
**12:21 [Kevin](https://slack.com/archives/C09D358F91R/p1772828503660079):** Caballo should be ID 0
**12:21 [Kevin](https://slack.com/archives/C09D358F91R/p1772828512900469):** Tanks are ID 1
**12:22 [Kevin](https://slack.com/archives/C09D358F91R/p1772828520509529):** Estes is ID 2
**12:22 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772828525525079):** Autobot lied to us
**12:22 [Kevin](https://slack.com/archives/C09D358F91R/p1772828539270229):** Not really
**12:22 [Kevin](https://slack.com/archives/C09D358F91R/p1772828550518499):** There are also Modbus addresses
**12:22 [Kevin](https://slack.com/archives/C09D358F91R/p1772828560921539):** Which it had correctly stated
**12:23 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772828596757309):** How can we test if it's working? Let me take a look
**12:23 [Kevin](https://slack.com/archives/C09D358F91R/p1772828631935129):** I tried putting it in hand on SCADA. Nothing came through
**12:24 [Kevin](https://slack.com/archives/C09D358F91R/p1772828653623299):** I'm thinking something is not enabled or fully programmed
**12:26 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772828761384849):** looking
**12:31 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772829098693939):** arent we reading everything from slave ID 1?
**12:31 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772829103259309):** isnt everything going through the one board?
**12:32 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772829148354059):** it looks like we're reading from ID 1.. i would think it would be 0. let me find your excel sheet you made
**12:35 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772829315564009):** i think we are reading everything from one board, and the one board is polling data from the others does that sound right?
**12:39 [Kevin](https://slack.com/archives/C09D358F91R/p1772829590784909):** Yes
**12:39 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772829591866579):** does this sound right? we are reading from like 600, 700,800
**12:40 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772829611182949):** so for bonita what would the register ranges be? its not in the spreadsheet i have
**12:41 [Kevin](https://slack.com/archives/C09D358F91R/p1772829671062869):** I don't know. Pretty sure I had that figured out, but I guess not. I will do some homework and we can hit this again next week
**12:41 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772829701298029):** sorry.. i can try the next set? maybe 900? i know this was in a spreadsheet.. but i dont seem to have it
**12:42 [Kevin](https://slack.com/archives/C09D358F91R/p1772829735202839):** Well if you have time I'll take a peek at my files
**12:42 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772829761136019):** yes i can take as much time as we need
**12:44 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772829860046529):** maybe im making sense of this document
**12:44 [Kevin](https://slack.com/archives/C09D358F91R/p1772829872330309):**
[[F0AKXK95ESC_Rancho_Ynecita_RFScada_IO_Record.pdf]]
**12:44 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772829892920849):** yeah thats what im looking at too.. i thought it was laid out different but maybe not
**12:47 [Kevin](https://slack.com/archives/C09D358F91R/p1772830031839399):** I'm glad I put some notes in there. I forgot that the cistern site is programmed to send Bonita back to Caballo as unit 21
**12:52 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772830351980169):** slowly coming back to me
**12:52 [Kevin](https://slack.com/archives/C09D358F91R/p1772830366005049):** Ya me too
**12:53 [Kevin](https://slack.com/archives/C09D358F91R/p1772830397850979):** Your AutoBot and vault will help us with this problem
**13:02 [Kevin](https://slack.com/archives/C09D358F91R/p1772830943243559):** I'm standing by
**13:02 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772830958213349):** data is really slow to update.. trying to make sense of whats coming in
**13:02 [Kevin](https://slack.com/archives/C09D358F91R/p1772830970844829):** Copy
**13:11 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772831488024979):** is it easy to confirm pressure? are you at the well?
**13:12 [Kevin](https://slack.com/archives/C09D358F91R/p1772831557426349):** I am
**13:12 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772831572627279):** can you tell me what the xmtr should read?
**13:13 [Kevin](https://slack.com/archives/C09D358F91R/p1772831612400469):** Psi is around 70
**13:14 [Kevin](https://slack.com/archives/C09D358F91R/p1772831652857949):** 0 to 200 scale
**13:15 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772831709086209):** ok im reading 67
**13:15 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772831722311479):** i think we're looking at the right data
**13:15 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772831724863639):** let me keep going
**13:15 [Kevin](https://slack.com/archives/C09D358F91R/p1772831732370899):** Thanks
**13:15 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772831739714369):** is the well on? is there flow?
**13:15 [Kevin](https://slack.com/archives/C09D358F91R/p1772831747406349):** No
**13:15 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772831753543089):** ok
**13:16 [Kevin](https://slack.com/archives/C09D358F91R/p1772831761583089):** I can run it
**13:16 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772831765060179):** not yet
**13:16 [Kevin](https://slack.com/archives/C09D358F91R/p1772831778537189):** Copy
**13:19 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772831973616589):** ok, if you can kick it on in hand lets see if we can read flow
**13:19 [Kevin](https://slack.com/archives/C09D358F91R/p1772831984492019):** Standby
**13:20 [Kevin](https://slack.com/archives/C09D358F91R/p1772832053103339):** Running 155 gpm
**13:21 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772832069874939):** no change yet.. but i think it takes a bit
**13:21 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772832082587319):** oh wait now i see 231
**13:21 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772832087166389):** i have it scalled 0-300
**13:21 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772832097027309):** 206 now
**13:21 [Kevin](https://slack.com/archives/C09D358F91R/p1772832115321389):** 148
**13:22 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772832154035809):** i have 219
**13:22 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772832158322279):** think its scalled 0-200?
**13:22 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772832169429039):** or wait.. higher?
**13:23 [Kevin](https://slack.com/archives/C09D358F91R/p1772832188380659):** Try 500
**13:23 [Kevin](https://slack.com/archives/C09D358F91R/p1772832235303089):** No 200
**13:24 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772832242275639):** yeah that went the wrong way
**13:24 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772832272626409):** 143
**13:24 [Kevin](https://slack.com/archives/C09D358F91R/p1772832277911549):** Bingo
**13:25 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772832300211819):** ok does this one have a well depth?
**13:25 [Kevin](https://slack.com/archives/C09D358F91R/p1772832304265439):** No
**13:25 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772832310479309):** amps/
**13:25 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772832311371889):** ?
**13:25 [Kevin](https://slack.com/archives/C09D358F91R/p1772832357262289):** Yes
**13:27 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772832459047069):** pressure still at 68-70?
**13:27 [Kevin](https://slack.com/archives/C09D358F91R/p1772832471799179):** 75
**13:28 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772832485434319):** i have it scalled 0-200
**13:28 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772832490826499):** im reading 68
**13:28 [Kevin](https://slack.com/archives/C09D358F91R/p1772832503908329):** Ok
**13:29 [Kevin](https://slack.com/archives/C09D358F91R/p1772832589259439):** Amps are 50
**13:31 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772832673101279):** im getting 42amps on 0-100
**13:31 [Kevin](https://slack.com/archives/C09D358F91R/p1772832699183649):** Ok we can check 0
**13:32 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772832746515379):** yeah lets kill it
**13:32 [Kevin](https://slack.com/archives/C09D358F91R/p1772832773336249):** Off
**13:33 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772832835629679):** no update yet
**13:35 [Kevin](https://slack.com/archives/C09D358F91R/p1772832921158089):** I have a digital output on for the cl2 pump
**13:35 [Kevin](https://slack.com/archives/C09D358F91R/p1772832929038519):** Now it's off
**13:35 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772832935286279):** ok it just updated
**13:35 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772832948568809):** 0 amps
**13:35 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772832951139909):** 0 gpm
**13:35 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772832955870109):** pressure says 66
**13:36 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772832963212699):** makes sense
**13:36 [Kevin](https://slack.com/archives/C09D358F91R/p1772832969675029):** Good enough
**13:36 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772832979891749):** ok, we need to test the well call
**13:36 [Kevin](https://slack.com/archives/C09D358F91R/p1772832983834609):** Yep
**13:36 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772832984588409):** and cl2 call
**13:36 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772832987387379):** standby
**13:36 [Kevin](https://slack.com/archives/C09D358F91R/p1772833009045259):** Cl2 seems like it was working
**13:39 [Kevin](https://slack.com/archives/C09D358F91R/p1772833164541069):** Well is on
**13:39 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772833169833469):** amazing
**13:39 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772833187150769):** do we also call cl2? let me look
**13:39 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772833192775059):** should it be on right now? if its in hand?
**13:39 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772833198517789):** ah. let me look at the lgoic
**13:40 [Kevin](https://slack.com/archives/C09D358F91R/p1772833200804059):** It's in auto
**13:40 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772833207075399):** SCADA hand
**13:40 [Kevin](https://slack.com/archives/C09D358F91R/p1772833211833869):** Copy
**13:40 [Kevin](https://slack.com/archives/C09D358F91R/p1772833227660719):** Cl2 should run after x flow
**13:40 [Kevin](https://slack.com/archives/C09D358F91R/p1772833245849539):** Just came on
**13:41 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772833301452249):** ah yes.
**13:41 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772833303880339):** all looking good
**13:42 [Kevin](https://slack.com/archives/C09D358F91R/p1772833345948289):** It's off
**13:42 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772833351392829):** amazing
**13:42 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772833376299879):** most tags are linked properly in scada. i need to update pressure and amps on the main page for bonita
**13:43 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772833414739749):** forgot how painfully slow it is to work on this system remotely
**13:43 [Kevin](https://slack.com/archives/C09D358F91R/p1772833425413569):** Ya
**13:45 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772833533577119):** ok.. loading the vtscada editor which takes like 10-15 minutes.. its crazy. i'll get those two tags updated.
**13:45 [Kevin](https://slack.com/archives/C09D358F91R/p1772833558016679):** Thank you!
**13:46 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772833578630949):** any thing else? ill set the total tags to rentetive while im here
**13:47 [Kevin](https://slack.com/archives/C09D358F91R/p1772833659742609):** Good idea. Maybe check setpoints and TOU? Should be good if you are using UDT or whatever they are called
**13:48 [Kevin](https://slack.com/archives/C09D358F91R/p1772833690878829):** Running to caballo
**13:48 [Kevin](https://slack.com/archives/C09D358F91R/p1772833736088459):** No, I think I'll drive instead
**13:49 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772833770713239):** haha
**13:57 [Kevin](https://slack.com/archives/C09D358F91R/p1772834224071999):** Scada board still thinks there's a comm fail
**13:57 [Kevin](https://slack.com/archives/C09D358F91R/p1772834244661429):** Is Estes in comm fail?
**13:59 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772834377209109):** No
**14:23 [Kevin](https://slack.com/archives/C09D358F91R/p1772835785476809):** @AutoBot set task for Mason to fix comm fail alarm to Bonita high priority 3/9 due date
**14:23 [AutoBot](https://slack.com/archives/C09D358F91R/p1772835786607239):** :mag: Searching the vault…
**14:23 [AutoBot](https://slack.com/archives/C09D358F91R/p1772835790328099):**
Task for Mason Radke: Fix the comm fail alarm for Bonita and set it to high priority.
Due date: March 9.
This task aligns with previous discussions about comm fail alarms and priority settings, such as the work Mason has done on comm fail logic and alarm notifications (see sources from Rancho-Ynecita 2025-12-02 and 2026-01-08, and Buellton 2026-02-16).
:card_file_box: *Sources* (10 chunks):
• *Rancho-Ynecita* — `Clients/Rancho-Ynecita/slack/2025/12/2025-12-02_rancho-ynecita.md`
• *Rancho-Ynecita* — `Clients/Rancho-Ynecita/slack/2026/01/2026-01-08_rancho-ynecita.md`
• *Buellton* — `Clients/Buellton/slack/2025/06/2025-06-11_buellton.md`
• *Buellton* — `Clients/Buellton/slack/2026/02/2026-02-16_buellton.md`
• *Buellton* — `Clients/Buellton/slack/2026/02/2026-02-06_buellton.md`
**14:23 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772835799516459):** try "add task" instead of set task
**14:23 [Kevin](https://slack.com/archives/C09D358F91R/p1772835832856899):** @AutoBot add task for Mason to fix comm fail alarm to Bonita high priority 3/9 due date
**14:23 [AutoBot](https://slack.com/archives/C09D358F91R/p1772835836068119):**
:white_check_mark: *Task created:* to fix comm fail alarm to Bonita 3/9
:bust_in_silhouette: Mason :star: High
[View in list](https://app.slack.com/lists/T089GAQQHTN/F09DBBTNQFJ/Rec0AK7G3U7T6)
**14:24 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772835851122199):** it probably needed to know the client also
**14:24 [Kevin](https://slack.com/archives/C09D358F91R/p1772835893177159):** @AutoBot set task for Mason to fix comm fail alarm to Bonita client waterworx high priority 3/9 due date
**14:24 [AutoBot](https://slack.com/archives/C09D358F91R/p1772835894142399):** :mag: Searching the vault…
**14:24 [AutoBot](https://slack.com/archives/C09D358F91R/p1772835899723469):**
There is no direct mention in the provided context about a task specifically for Mason Radke to fix a comm fail alarm for the Bonita client Waterworx with a high priority and a due date of 3/9.
However, Mason Radke has been involved in working on communication fail alarms and related logic for various clients, including setting up comm fail logic, alarm notifications, and delays (see Rancho Ynecita on 2025-12-02 and 2026-01-08, and Buellton in 2026-02). There is also mention of comm fail alarms being set up and tested by Mason.
To set a task for Mason Radke to fix the comm fail alarm for the Bonita client Waterworx with high priority and due date 3/9, you would typically create a task in your project management or communication tool (e.g., Slack, email, task tracker) with the following details:
- Task: Fix comm fail alarm for Bonita client Waterworx
- Assigned to: Mason Radke
- Priority: High
- Due date: March 9
Since the context does not show an existing task with these exact details, you can create this task manually in your system or notify Mason via your communication channel.
If you want, I can help draft a message for assigning this task to Mason. Would you like that?
:card_file_box: *Sources* (10 chunks):
• *Rancho-Ynecita* — `Clients/Rancho-Ynecita/slack/2025/12/2025-12-02_rancho-ynecita.md`
• *Rancho-Ynecita* — `Clients/Rancho-Ynecita/slack/2026/01/2026-01-08_rancho-ynecita.md`
• *Buellton* — `Clients/Buellton/slack/2026/02/2026-02-06_buellton.md`
• *Buellton* — `Clients/Buellton/slack/2026/02/2026-02-16_buellton.md`
• *SSLOCSD* — `Clients/SSLOCSD/emails/2026/march/Sludge_Pump_Alarm_Investigation_Report.md`
**14:25 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772835904349749):** "set task" again
**14:25 [Kevin](https://slack.com/archives/C09D358F91R/p1772835905512679):** Shit
**14:25 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772835915154419):** i can make it smarter..
**14:25 [Kevin](https://slack.com/archives/C09D358F91R/p1772835924787279):** @AutoBot add task for Mason to fix comm fail alarm to Bonita client waterworx high priority 3/9 due date
**14:25 [AutoBot](https://slack.com/archives/C09D358F91R/p1772835926030929):**
:white_check_mark: *Task created:* to fix comm fail alarm to Bonita client waterworx 3/9
:bust_in_silhouette: Mason :star: High :office: Waterworx
[View in list](https://app.slack.com/lists/T089GAQQHTN/F09DBBTNQFJ/Rec0AK1SDBJKG)
**14:31 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772836304386329):** ok, tags fixed on scada. looking into comm fail
**14:35 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772836518080669):** comm fail bit was off by one register for bonita
**14:39 [Kevin](https://slack.com/archives/C09D358F91R/p1772836751545969):** Copy!
**14:39 [Kevin](https://slack.com/archives/C09D358F91R/p1772836760989399):** We good?
**14:39 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772836790758069):** i believe so. other than reporting. but i still need to decide how to put a bow on that
**14:40 [Kevin](https://slack.com/archives/C09D358F91R/p1772836814789739):** Fabulous.
**14:40 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772836834418599):** totalizer tags were already retentive.. if they zero out again we'll have to do a deeper dive
**14:40 [Kevin](https://slack.com/archives/C09D358F91R/p1772836851495259):** Copy
**14:41 [Kevin](https://slack.com/archives/C09D358F91R/p1772836880675789):** I changed a setting in the Bluetti that was likely shutting it down during a power outage
**14:41 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772836890400109):** Oh good find
**14:41 [Kevin](https://slack.com/archives/C09D358F91R/p1772836900548199):** I didn't know it had settings lol
**14:41 [Mason Radke](https://slack.com/archives/C09D358F91R/p1772836911117599):** Surprised it doesn’t have AI
**14:42 [Kevin](https://slack.com/archives/C09D358F91R/p1772836934403319):** Lol