# HCA Middle Well Bid notes Questions: - Why is there a PRV on the well line? You have a VFD.- Suggest VFD and soft starter to be installed together in a climate controlled cabinet. N4X VFDs are expensive and hard to get.- Is Nema4X necessary for electrical cabinets?- Are individual conduits necessary for each instrument?- How deep is the well pump? Suggest dv/dt filter on output of VFD- Suggest semiconductor high-speed fuses on input to VFD- Suggest adding a MCP to the power input side of the RVSS to allow for LOTO- Is VFD input isolation contactor necessary? Bypass function can operate the output contactors, and power can be isolated manually. - Radios are Cambium Networks (need model) Materials & Subs: Antenna tower Sent email to Advanced Technology Group Pump PanelDrawing sht 20 PLC PanelPLC - AI-5 / DI-18 / DO-5 / AO-3 AB CompactLogixneed 25% sparesThey missed the IO for the chemical pumps. I added them to the totalsNetwork drawing sht 24Layout drawings sht 25 - 27Wiring drawings sht 28 - 34Spec section 406100 1.01.E.d.4 states all motor control devices shown on the schematics to be installed in the PLC panel Radio Panel sht 35 SCADA Integration / Programming allowance shown to be \$85k in bid form Panels are separate from the integration/programming. I am only contracting with the city for the integration/programming. ExclusionsThe supply and/or installation of any and all conduit, wire, coax, and fiber optic cable. Scope: Pre con meeting Testing / Training:Testing plan (PLC/HMI/SCADA)Training plan (PLC/HMI)Pre-startup testing (01 75 17 - 3) includes PLC to SCADAStart-up / Field TestingOperational Demonstration Test (8hrs) 01 75 17 Control Narrative HMI Screens SCADA Screens Loop Drawings ?? Instrument installation details ?? Instrument calibration and configuration 406100-1.04 gives a good overview of the PCS supplier general requirements. Close-outO&M Manual (PLC/HMI)

Extracted Entities

TypeKeyValueConfidenceEvidence
site Client Name Solvang-Water 100% Client: Solvang-Water
system PLC Product AB CompactLogix 90% PLC - AI-5 / DI-18 / DO-5 / AO-3 AB CompactLogix
system Radio Product Cambium Networks 80% Radios are Cambium Networks (need model)
File: Clients/Solvang-Water/evernote/HCA_Middle_Well_Bid_notes.md
Updated: 2026-03-31 15:26:41.994829