Content
# HCA Well
201006
Changed scaling of new cl2 analyzer.
Changed measurement range from 5 to 10
![[img_20201005_114226.237.jpg]]
![[img_20201005_114217.574.jpg]]
![[img_20201005_114207.467.jpg]]
New Nh3 pump
![[img_20200812_145503.972.jpg]]
Level transmitter In-Situ LevelTroll 400
Absolute psi. 14.6 psi 33.7ft is zero
Range is 0 to 300 psia
PLC zero is 7475 4.79ma