# SCADA Comm Notes Found how the reservoir levels are transmitted to the sites. Gateway Event Scripts in SCADA. ![[SCADA_Comm_Notes_Snapshot.jpg]] Except for W22 and Res1, which are written to by ModbusTCP comm from Res2 NEED PLC PROGRAMS FROM RES 1 AND RES 3 Res 3 level is transmitted to Well 3 by the old Phoenix IO radios and is input to the 820 on input 2 [this code is there, but not used] THE "TRUE" BIT INPUTS TO THE COPY AND MODBUS MSG BLOCKS IN THE COMMS PROGRAMS IN WELL 4, 3, AND 7 WERE ALL UNCONNECTED.  THIS SAYS THE MODBUS COMM TO WRITE THE LEVELS FROM RES 1 AND RES 3 ARE IN ANOTHER PLC THAT WRITES TO THE "res_1_level" and "res_3_level" tags. THEN MAYBE SCADA PICS IT UP AND DISTRIBUTES IT? NEED TO INVESTIGATE RES 1 AND RES 3 PLC TO SEE IF THEY WRITE THE LEVELS LIKE RES 2 DOES. I WONDER IS RES 1 AND RES 3 WRITE THEIR LEVELS TO RES 2. PROBABLY NOT. BOTH RES 1 AND RES 3 TAGS IN THE PLC ARE 0 WELL 3 HAS RES 1 AND RES 3 LEVELS DATA IN THE TAGS LOOK IN RES 1 AND RES 3 PLC TO SEE IF THEY ARE WRITING THEIR LEVELS TO W3, AND W4. THEN MAYBE THE WRITE TO WELL 7 IS DISABLE OR MISSING? RES 2 PLC WRITES THE TANK LEVEL TO RES 1 PLC AND W22 PLC THESE ARE THE ONLY TWO SITES THAT RUN OFF OF RES 2 LEVEL ?? THERE ARE TWO MODBUS WRITE COMM BLOCKS MSG_MODBUS2_RES1 LOCAL CONFIGLOCAL CHANNEL #4TRIGGER ONCEMODBUS COMMAND 161 ELEMENT TARGET CONFIGTARGET'S MODBUS DATA ADDRESS = 11TARGET NODE ADDRESS = 192.168.100.111TARGET PORT 502UNIT IDENTIFIER = 1 LOCAL ADDRESSLOCALADDR = 1277 MSG_MODBUS2_W22 LOCAL CONFIGLOCAL CHANNEL #4TRIGGER ONCEMODBUS COMMAND 161 ELEMENT TARGET CONFIGTARGET'S MODBUS DATA ADDRESS = 16 [40016?] LOOKS LIKE N11:15 IN W22 PLCTARGET NODE ADDRESS = 192.168.100.150TARGET PORT 502UNIT IDENTIFIER = 1 LOCAL ADDRESSLOCALADDR = 1277 MODBUS MAPPING POINTS OF INTEREST:400035-36 RES_1_LEVEL (REAL)400037-38 RES_3_LEVEL (REAL) IN WELL 22 PLC MODBUS HOLDING REG ARE IN N11 AND COILS ARE B3

Extracted Entities

TypeKeyValueConfidenceEvidence
server Modbus Unit Identifier 1 100% UNIT IDENTIFIER = 1
server Modbus Target Node Address for RES1 192.168.100.111 100% TARGET NODE ADDRESS = 192.168.100.111
server Modbus Target Port for RES1 502 100% TARGET PORT 502
server Modbus Target Node Address for W22 192.168.100.150 100% TARGET NODE ADDRESS = 192.168.100.150
server Modbus Target Port for W22 502 100% TARGET PORT 502
server Modbus Command 161 90% MODBUS COMMAND 161
server Modbus Data Address for RES1 11 80% TARGET'S MODBUS DATA ADDRESS = 11
server Modbus Data Address for W22 16 80% TARGET'S MODBUS DATA ADDRESS = 16
site Client Name Solvang-Water 100% Client: Solvang-Water
site Reservoir Sites RES1, RES2, RES3, W22, WELL3, WELL4, WELL7 90% Except for W22 and Res1... Res 3 level... WELL 3... WELL 4... WELL 7
system PLC Communication Protocol ModbusTCP 100% written to by ModbusTCP comm from Res2