Content
# SCADA Work Log
210310
Performed Windows updates on PC2
210223
Getting to know the new SCADA software
Changed Jay's password and Roles
Added a login for me
poked around the Designer and configuration
added a tag in HCA for the door alarm.
changed password of the cellular modem
changed SCADA System Fail sms #
190806
Complete comm loss to Res 2 Booster
Rebooted Res1 PLC
No level alarms from Res 2
Logic is good. Dialer alarms needed to be cleared.
190627
Adjusted timeouts on MSG blocks to 2 sec from 10 sec.
190624
Started network investigation.
Put internet on the unused ethernet port on the computer to separate it from the SCADA net.
190130
configured FT Network Directory. User name "Solvang Water SCADA" pw "Chort654!"
added W21 chlorine residual scaling calculation to "Analog_in" routine in W4 PLC
added W21 chlorine residual alarm setpoint entry to "Alarms" screen
Removed Rate-of-change control from the W21 pump control logic "CTRL_Well_21" and added Res 2 tank level setpoint control logic