# Well #21 & Reservoir 2 140610 Adding Well #21 to SCADA Control Narative Control well based on tank level, rate of tank level drop Objective is to only run the well when water is leaving the tank. Using Rate of Change calculation from an ALMA block in the PLC. - Start well 21 if ROC is not positive for 10 min and Res 2 level is between the Well 21 on and off setpoints.- Stop well 21 if ROC is positive for 10 min or Res 2 level reaches the Well 21 off setpoint. Chloramination control- Start hypo and ammonia pumps when well starts. Monitor- Well flow rate (well running when flow > sp) Tank 2 level Hypo pump pulse Ammonia pump pulse Existing wiring from the well to Block Wall      Flow signal      120 V Start signal I/O Needed- | Type | Tag | Terminal(s) | PLC Point | SCADA Tag | | --- | --- | --- | --- | --- | | DI | HYPO_PLS | | | | | DI | AMNA_PLS | | | | | DO | WELL_CALL | | | | | DO | CHEM_CALL | | | | | AI | WELL_FLOW | | | | PLC IP 192.168.100.130 Radio IP 192.168.100.230 Comms W4 PLC handles communication and control. Reads N17:0 to N17:9 Stores in R2_Read Writes R2_Write 0-9 Stores in N16:0 Flow rate calculation Flow meter range 0-1000 gpm AI range 6250 - 20000 (13750) Rate Of Change control Using a ALMA alarm block in RSLogix to calculate the ROC of Res 2 in inches per second.Instruction Help:Calculated rate-of-change of the In value. This value is updated when the instruction is scanned following each elapsedROCPeriod. The ROC value is used to evaluate the ROCPosInAlarm and ROCNegInAlarm conditions.ROC = (current sample of In – previous sample of In) / ROCPeriod. HMI Notes Add indicators for W21.Chemical_Pump_Failure and General Alarm W21_Gen_ALM Setpoint for W21.Delay_Timer[0].pre Indicator for W21.Delay_Timer[0].acc Indicator for R2_Write[0].4 (Well start d.o.) Indicator for R2_Write[0].5 (Chem start d.o.) Indicator for local hoa Alarms Well Fail W21_Failure_Alarm.InAlarm Ammonia Pump Fail W21_Ammonia_Failure.InAlarm Chlorine Pump Fail W21_Chlorine_Pump_Failure.InAlarm

Extracted Entities

TypeKeyValueConfidenceEvidence
server PLC IP 192.168.100.130 100% PLC IP 192.168.100.130
server Radio IP 192.168.100.230 100% Radio IP 192.168.100.230
site Client Name Solvang-Water 100% Client: Solvang-Water
site Well Name Well #21 100% Adding Well #21 to SCADA
site Reservoir Name Reservoir 2 100% Well #21 & Reservoir 2
system PLC Software RSLogix 90% Using a ALMA alarm block in RSLogix to calculate the ROC
File: Clients/Solvang-Water/evernote/Well_21_Reservoir_2_1.md
Updated: 2026-04-17 01:51:28.493020