# #ccsd-water-ignition — 2026-04-20
**08:55 [Mason Radke](https://slack.com/archives/C08TVA84PD4/p1776700533706889):**
[[F0AU30DP7R8_CCSD_Data_Collector_67.html]]
**08:55 [Mason Radke](https://slack.com/archives/C08TVA84PD4/p1776700556645279):** @andy documentation updated to include per site read and write disable commands
**08:56 [andy](https://slack.com/archives/C08TVA84PD4/p1776700585493069):** Beautiful thank you
**08:56 [Mason Radke](https://slack.com/archives/C08TVA84PD4/p1776700588697269):** comm routine is 177 rungs
**08:56 [andy](https://slack.com/archives/C08TVA84PD4/p1776700609975169):** Actual logic is like 15
**08:57 [Mason Radke](https://slack.com/archives/C08TVA84PD4/p1776700626779269):** haha yah.
**08:58 [andy](https://slack.com/archives/C08TVA84PD4/p1776700707162379):** That’s the same proportion of overtime and service call cost
**09:00 [Mason Radke](https://slack.com/archives/C08TVA84PD4/p1776700843219659):** sounds about right.. i still need to go through all the function block and update the inp_PVBad or IOfault with the disable commands
**09:00 [Mason Radke](https://slack.com/archives/C08TVA84PD4/p1776700847227339):** gonna take a minute
**09:01 [Mason Radke](https://slack.com/archives/C08TVA84PD4/p1776700895669299):** but for your scada work you should be good to
**09:01 [Mason Radke](https://slack.com/archives/C08TVA84PD4/p1776700899062989):** using that latest HTML
**09:02 [andy](https://slack.com/archives/C08TVA84PD4/p1776700925258099):** Right thank you
**09:08 [andy](https://slack.com/archives/C08TVA84PD4/p1776701332475739):** My client is saying rodeo grounds pumps are turning on and off every 10 seconds or so
**09:09 [Mason Radke](https://slack.com/archives/C08TVA84PD4/p1776701344940419):** thats not good. let me take a look
**09:09 [andy](https://slack.com/archives/C08TVA84PD4/p1776701352888969):** Maybe you have the enable bit mapped wrong or something
**09:16 [Mason Radke](https://slack.com/archives/C08TVA84PD4/p1776701778155419):** it was enabled.. my per site logic did a one shot enabling everything.
**09:16 [Mason Radke](https://slack.com/archives/C08TVA84PD4/p1776701782228289):** i need to shut down the writes again
**09:18 [Mason Radke](https://slack.com/archives/C08TVA84PD4/p1776701914755699):** ok, all writes disabled.
**09:18 [Mason Radke](https://slack.com/archives/C08TVA84PD4/p1776701930953969):** using the new per site write disable commands
**09:19 [andy](https://slack.com/archives/C08TVA84PD4/p1776701941403109):** Ok
**09:19 [andy](https://slack.com/archives/C08TVA84PD4/p1776701948300289):** I’ll have them out into auto and test
**09:23 [andy](https://slack.com/archives/C08TVA84PD4/p1776702184578009):**
![[F0AU15P2154_IMG_1411]]
**09:23 [Mason Radke](https://slack.com/archives/C08TVA84PD4/p1776702196304379):** excellent
**09:23 [Mason Radke](https://slack.com/archives/C08TVA84PD4/p1776702215660859):** good end-2-end test right there.
**09:23 [Mason Radke](https://slack.com/archives/C08TVA84PD4/p1776702217023589):** we have control
**09:24 [Mason Radke](https://slack.com/archives/C08TVA84PD4/p1776702291620179):**
[[F0AU6RCJWS0_CCSD_Data_Collector_68.html]]
**13:00 [Kevin](https://slack.com/archives/C08TVA84PD4/p1776715237914789):** wonder why they were going on and off
**13:01 [Mason Radke](https://slack.com/archives/C08TVA84PD4/p1776715280783009):** I’m sure local logic was telling it to run and we were writing a stop command to it
**13:01 [Mason Radke](https://slack.com/archives/C08TVA84PD4/p1776715289984249):** It’s a pulse on pulse off set up
Extracted Entities
| Type | Key | Value | Confidence | Evidence |
| contact |
Mason Radke |
Mason Radke |
100% |
08:55 [Mason Radke](https://slack.com/archives/C08TVA84PD4/p1776700533706889) |
| contact |
andy |
andy |
100% |
08:56 [andy](https://slack.com/archives/C08TVA84PD4/p1776700585493069) |
| contact |
Kevin |
Kevin |
100% |
13:00 [Kevin](https://slack.com/archives/C08TVA84PD4/p1776715237914789) |
| site |
Rodeo Grounds Pumps |
Rodeo Grounds |
90% |
My client is saying rodeo grounds pumps are turning on and off every 10 seconds |
| system |
SCADA System |
SCADA |
80% |
but for your scada work you should be good to using that latest HTML |
File: Clients/Tough/CCSD/slack/2026/04/2026-04-20_ccsd-water-ignition.md
Updated: 2026-04-20 20:15:10.740040