| server |
Digi One IAP Network Protocol |
EtherNet/IP |
100% |
Network Side: Set the Master protocol to EtherNet/IP |
| server |
Digi One IAP Serial Protocol |
Modbus RTU |
100% |
Serial Side: Set the Slave protocol to Modbus RTU |
| server |
Digi One IAP Serial Port |
DB9 port (Pins 3/Data+ and 4/Data-) |
90% |
Digi Side: Use the DB9 port (Pins 3/Data+ and 4/Data- are standard for 2-wire 485 |
| server |
ABB ACS550 VFD Terminals |
Terminals 28 (B+), 29 (A-), and 30 (AGND) |
90% |
ABB ACS550 Side: Wire to Terminals 28 (B+), 29 (A-), and 30 (AGND) |
| server |
Digi One IAP IP Address |
IP Address of the Digi One IAP |
70% |
Hop 1: IP Address of the Digi One IAP |
| site |
Client Plant |
Buellton |
100% |
Client: Buellton |
| system |
Gateway Device |
Digi One IAP |
100% |
conversion of your existing Digi One IAP gateway |
| system |
Variable Frequency Drives |
ABB ACS550 VFDs |
100% |
two ABB ACS550 VFDs via Modbus RS-485 |
| system |
PLC Controller |
MicroLogix 1100 |
100% |
bridge communications between a MicroLogix 1100 and two ABB ACS550 VFDs |
| task |
ACS550 Register Mapping |
40001: Control Word; 40002: Speed Reference; 40004/40005: Status Word and Actual Speed |
100% |
Register Mapping (ACS550): 40001 Control Word, 40002 Speed Reference, 40004/40005 Status Word |
| task |
Digi One IAP DIP Switch Settings |
Sw 1: ON, Sw 2: OFF, Sw 3: ON, Sw 4: ON |
100% |
Set for RS-485 2-wire (Standard config: Sw 1: ON, Sw 2: OFF, Sw 3: ON, Sw 4: ON) |
| task |
ABB ACS550 VFD Parameter 9802 |
1 (STD MODBUS) |
100% |
9802 (Comm Protocol): Set to 1 (STD MODBUS) |
| task |
ABB ACS550 VFD Station IDs |
VFD #1 = 1, VFD #2 = 2 |
100% |
5302 (Station ID): Set VFD #1 to 1 and VFD #2 to 2 |
| task |
ABB ACS550 VFD Baud Rate |
19.2k |
100% |
5303 (Baud Rate): Set to 19.2k (or match Digi settings) |
| task |
Digi One IAP Message Mapping |
Map N10 to Unit ID 1, Map N11 to Unit ID 2 |
100% |
Map N10: To Modbus Unit ID 1; Map N11: To Modbus Unit ID 2 |
| task |
MicroLogix 1100 MSG Instructions |
Use SLC Typed Read/Write with Multi-Hop enabled |
100% |
MSG Instructions: Use SLC Typed Read/Write instructions; Multi-Hop enabled |
| task |
ABB ACS550 VFD Control Profile |
0 (ABB DRV LIM) or 2 (DCU PROFILE) |
90% |
5305 (Control Profile): Set to 0 (ABB DRV LIM) or 2 (DCU PROFILE) |
| task |
ABB ACS550 VFD Parity |
8 None 1 or 8 Even 1 |
90% |
5304 (Parity): Set to 8 None 1 (or 8 Even 1, provided it is consistent) |