# #solvang-ww — 2025-09-30 **08:46 [Kevin](https://slack.com/archives/C08HMJX8J4F/p1759247177282639):** I think this power supply in the middle comes out. @Mason Radke Can you confirm that for me? ![[F09HV73PGG5_20250930_084417.jpg]] **08:47 [Mason Radke](https://slack.com/archives/C08HMJX8J4F/p1759247271239509):** lets see what i can find **08:52 [Mason Radke](https://slack.com/archives/C08HMJX8J4F/p1759247558750309):** yes.. leave as is.. power supply needed. **08:52 [Mason Radke](https://slack.com/archives/C08HMJX8J4F/p1759247562209959):** simply replace the PLC **08:57 [Kevin](https://slack.com/archives/C08HMJX8J4F/p1759247851007399):** Oh ok! **08:58 [Kevin](https://slack.com/archives/C08HMJX8J4F/p1759247899688139):** Any power needed to be connected to the plc? **08:58 [Mason Radke](https://slack.com/archives/C08HMJX8J4F/p1759247920218699):** likely.. yes.. let me see if i can confirm **09:04 [Mason Radke](https://slack.com/archives/C08HMJX8J4F/p1759248268585019):** are there power terminals on the L320ER? **09:04 [Mason Radke](https://slack.com/archives/C08HMJX8J4F/p1759248281321479):** it sounds like it gets power from the backplane.. and no external power is required. **09:43 [Kevin](https://slack.com/archives/C08HMJX8J4F/p1759250634878249):** Still looking? **09:44 [Mason Radke](https://slack.com/archives/C08HMJX8J4F/p1759250660874129):** no, i was waiting to hear back from you **09:44 [Mason Radke](https://slack.com/archives/C08HMJX8J4F/p1759250666792409):** are there power terminals on the L320ER? **09:44 [Mason Radke](https://slack.com/archives/C08HMJX8J4F/p1759250680070049):** it sounds like it gets power from the backplane and no external power is required.. **09:44 [Kevin](https://slack.com/archives/C08HMJX8J4F/p1759250684152149):** Yes **09:44 [Kevin](https://slack.com/archives/C08HMJX8J4F/p1759250691807039):** MOD and SA **09:44 [Mason Radke](https://slack.com/archives/C08HMJX8J4F/p1759250696931099):** thats what i remember also. **09:45 [Mason Radke](https://slack.com/archives/C08HMJX8J4F/p1759250704337099):** and i feel like we need to power it.. but my reading is saying otherwise **09:45 [Mason Radke](https://slack.com/archives/C08HMJX8J4F/p1759250729627739):** let me look at the manual for the L320ER directly **09:45 [Kevin](https://slack.com/archives/C08HMJX8J4F/p1759250741654829):** Thanks **10:10 [Kevin](https://slack.com/archives/C08HMJX8J4F/p1759252211437249):** I can't seem to add 1769 IO to a studio IO configuration **10:13 [Mason Radke](https://slack.com/archives/C08HMJX8J4F/p1759252412571019):** they are 1769 modules? **10:13 [Kevin](https://slack.com/archives/C08HMJX8J4F/p1759252418125199):** Yes **10:13 [Mason Radke](https://slack.com/archives/C08HMJX8J4F/p1759252422116519):** is the l320Er 5069? **10:13 [Kevin](https://slack.com/archives/C08HMJX8J4F/p1759252428102689):** Yes **10:14 [Mason Radke](https://slack.com/archives/C08HMJX8J4F/p1759252449168679):** ummm **10:14 [Mason Radke](https://slack.com/archives/C08HMJX8J4F/p1759252454184319):** im confused **10:14 [Mason Radke](https://slack.com/archives/C08HMJX8J4F/p1759252457504249):** standby **10:19 [Mason Radke](https://slack.com/archives/C08HMJX8J4F/p1759252774415219):** bad news. **10:19 [Mason Radke](https://slack.com/archives/C08HMJX8J4F/p1759252789379449):** moving from *L33E (5370)* to *L320ER (5380)*, your 1769 Compact I/O modules *cannot be reused directly* with the new controller. The L320ER is a *5380 series*, which requires *5069 Compact I/O* modules. **10:20 [Mason Radke](https://slack.com/archives/C08HMJX8J4F/p1759252804259649):** i dont know why this information wasnt more obvious when i first started looking into it **10:21 [Kevin](https://slack.com/archives/C08HMJX8J4F/p1759252872786019):** Ok. Back to the drawing board **10:22 [Mason Radke](https://slack.com/archives/C08HMJX8J4F/p1759252961959359):** yeah that sucks **10:23 [Mason Radke](https://slack.com/archives/C08HMJX8J4F/p1759252986477049):** what about converting that IO rack to Remote IO.. if there is a network adapter that works with 1769 modules **10:24 [Mason Radke](https://slack.com/archives/C08HMJX8J4F/p1759253075324849):** *1769-AENTR* **10:24 [Mason Radke](https://slack.com/archives/C08HMJX8J4F/p1759253086891329):** will turn that IO rack into remote IO that the L320ER can use

Extracted Entities

TypeKeyValueConfidenceEvidence
contact Person Kevin 100% **08:46 [Kevin]** I think this power supply in the middle comes out.
contact Person Mason Radke 100% **08:47 [Mason Radke]** lets see what i can find
site Client Name Solvang-WW 100% Client: Solvang-WW
system I/O Modules Old 1769 Compact I/O 90% your 1769 Compact I/O modules *cannot be reused directly*
system I/O Modules New 5069 Compact I/O 90% The L320ER is a *5380 series*, which requires *5069 Compact I/O* modules
system PLC Model New L320ER (5380) 90% moving from *L33E (5370)* to *L320ER (5380)*
system PLC Model Old L33E (5370) 90% moving from *L33E (5370)* to *L320ER (5380)*
system Network Adapter 1769-AENTR 80% *1769-AENTR* will turn that IO rack into remote IO